| Plan Review Notes For Permit 05010074 |
| Permit Number |
05010074 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-24 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)DECLARE AN OCCUPANCY TYPE FOR NEW | | | AND EXISTING AREAS FBC CHAPTER 3. | | | | | | 2.)SHOW COMPLIANCE WITH FBC 704, | | | OCCUPANCY SEPARATIONS.INCLUDE | | | INFORMATION FOR THE DOORS (FIRE RATING) | | | AS REQUIRED. | | | | | | 3.)PROVIDE INFORMATION IN REGARDS TO | | | CHEMICALS TO BE USED IN THE MIXING ROOM | | | AND SPRAY BOOTHS; MSDS IF NECESSARY. | | | WHERE WILL PAINT BE STORED? | | | (INFORMATION | | | PERTINENT TO OCCUPANCY, STORAGE OF | | | COMBUSTIBLE MATERIALS).ALSO SEE FBC | | | TABLE 308.2; SHOW COMPLIANCE ON THE | | | PLAN. | | | | | | 4.)PROVIDE STRUCTURAL DETAILS FOR THE | | | MIXING ROOM AND SPRAY BOOTH.THE FLOOR | | | PLAN DOES NOT SHOW DOORS FOR THE MIXING | | | ROOM, WALL SECTIONS ARE NOT ON THE | | | PLAN. | | | | | | 5.)SHEET 1, CODE INFORMATION, LISTS | | | THREE DIFFERENT BUILDING CODES (FBC, | | | UBC | | | AND IBC).PLEASE REFER TO THE CORRECT | | | BUILDING CODE ONLY, FBC 2001 WITH | | | AMENDMENTS. | | | | | | 6.)THE SEAL IS TO BE DATED AND THE CA | | | NUMBER FOR MOLVET ENGINEERING LLC IS TO | | | BE ON THE TITLE BLOCK, FAC61G15-23.002. |
|