| Plan Review Notes For Permit 05010037 |
| Permit Number |
05010037 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-21 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)IF WINDOWS ARE REPLACED, PRODUCT | | | APPROVALS AND IMPACT PROTECTION | | | REQUIRED.EITHER SUBMIT PRODUCT | | | APPROVALS/TEST REPORTS OR REMOVE THAT | | | WORK FROM THE PERMIT APPLICATION. | | | | | | 2.)PROVIDE A SPECIFICATION (DETAIL - | | | WALL SECTION IF APPLICABLE) FOR REPAIR. | | | SCOPE OF WORK SHOULD BE CLEAR ON | | | BUILDING PLANS.NO PLANS SUBMITTED. | | | | | | 3.)PLEASE SCHEDULE A PREINSPECT, RYAN | | | NUQUIST, CHIEF STRUCTURAL INSPECTOR, | | | 805-6666. | | | | | | 4.)THE NOTICE OF COMMENCEMENT DOES NOT | | | INCLUDE WINDOWS IN THE SCOPE OF WORK. |
|