Plan Review Notes
Plan Review Notes For Permit 05010022
Permit Number 05010022
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-15 00:00:00DENIED;
 1.RISER DIAGRAMS ARE NOT TO CODE.
 KITCHEN SINK AND W/M ARE REQUIRED TO
 DISCHARGE DOWN STREAM OF A BATH ROOM
 GROUP SEC 909.1. KITCHEN SINK SHOULD BE
 A MECHANICAL VENT. NO WALL FOR VENT
 PIPE.
 2.MASTER BATHROOM RISER. PIPE SIZING
 MUST BE 3" DOWN STREAM OF A TOILET.
 DRAWING A TRAP FOR THE WATER CLOSET IS
 NOT REQUIRED. THE TRAP IS IN THE TOILET.
 PLEASE SEE RED LINE ON PLUMBING PAGE.
 3.PLEASE CHANGE NOT 15 TO SHOCK
 ARRESTORS TO BE INSTALLED PER SEC 604.9
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695