| Plan Review Notes For Permit 05010021 |
| Permit Number |
05010021 |
|
| Review Stop |
E |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2006-02-24 00:00:00 | *** UNSAT *** | | | | | | | | | ** PLEASE KNOW, ARCHITECT HAS BEEN | | | CONTACTED ON 2/24/06 AND COMMENTS WERE | | | GONE OVER IN ORDER TO ALLEAVIATE ANY | | | QUESTIONS, OR CONCERNS OVER THE | | | CORRECTIONS AND WHAT IS NEEDED. | | | | | | 1)NOTE: PLEASE SEE RISER METER MAIN NOW | | | DOES NOT INDICATE ANY OCP FOR EACH OF | | | THE TWO PANELS? | | | PLEASE SHOW.215.5,240.4,310.16 ETC | | | | | | 2)NOTE: PLEASE SEE MISSING EGRESS LTS, | | | LOGGIA, ENTRY, PLEASE KNOW, SOME SORT OF | | | FIXTURE IS REQUIRED. LS 101 7.8, NEC | | | 210.70 | | | | | | 3)NOTE: PLEASE SEE THE DEDICATED BATHS | | | ARE NOW SHOWN AS 15A, WHERE CODE | | | REQUIRES A MIN OF 20A #12. 210.11C3 | | | | | | 4)NOTE: PLEASE SEE LAUNDRY CIRCUIT NOW | | | INDICATES1200 VA FOR LOAD. PLEASE SEE | | | 220.16, WHICH REQUIRES A MIN OF 1500VA. | | | | | | PLEAS ESUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|