Plan Review Notes
Plan Review Notes For Permit 05010021
Permit Number 05010021
Review Stop E
Sequence Number 8
Notes
Date Text
2006-02-24 00:00:00*** UNSAT ***
  
  
 ** PLEASE KNOW, ARCHITECT HAS BEEN
 CONTACTED ON 2/24/06 AND COMMENTS WERE
 GONE OVER IN ORDER TO ALLEAVIATE ANY
 QUESTIONS, OR CONCERNS OVER THE
 CORRECTIONS AND WHAT IS NEEDED.
  
 1)NOTE: PLEASE SEE RISER METER MAIN NOW
 DOES NOT INDICATE ANY OCP FOR EACH OF
 THE TWO PANELS?
 PLEASE SHOW.215.5,240.4,310.16 ETC
  
 2)NOTE: PLEASE SEE MISSING EGRESS LTS,
 LOGGIA, ENTRY, PLEASE KNOW, SOME SORT OF
 FIXTURE IS REQUIRED. LS 101 7.8, NEC
 210.70
  
 3)NOTE: PLEASE SEE THE DEDICATED BATHS
 ARE NOW SHOWN AS 15A, WHERE CODE
 REQUIRES A MIN OF 20A #12. 210.11C3
  
 4)NOTE: PLEASE SEE LAUNDRY CIRCUIT NOW
 INDICATES1200 VA FOR LOAD. PLEASE SEE
 220.16, WHICH REQUIRES A MIN OF 1500VA.
  
 PLEAS ESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]