| Date |
Text |
| 2006-01-30 00:00:00 | ********** UNSAT ************ |
| | |
| | |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER, PLANS |
| | AND PANEL SCHEDULES SUBMITTED, PLEASE |
| | SEE THERE ARE NUMEROUS ITEMS WHICH DO |
| | NOT MATCH. |
| | |
| | A) PLEASE SEE RISER SHOWS A PANEL "C", |
| | HOWEVR NO PANEL SCHEDULE WAS SUBMITTED |
| | FOR THIS AND THIS IS NOT SHOWN ON PLANS? |
| | |
| | B)PLEASE SEE WHAT APPEARS TO INDICATE A |
| | 400A SERVICE NOW WITH METER MAIN, SHOWS |
| | TWO-200A BRKRS, BUT ALSO SHOWS FEED THRU |
| | LUGS FOR ONE?? ETC??? |
| | |
| | C)PLEASE SEE A POOL PANEL IS SHOWN ON |
| | RISER BUT NOT ON PLANS. PLEASE SEE A |
| | POOL PUMP IS SHOWN ON PANEL "B"?? VERIFY |
| | OF POOL PUMP IS NOT FED FROM POOL PANEL. |
| | |
| | D)PLEASE SEE NOW SERVICE INDICATES TO |
| | FPL HAN-HOLE, PLEASE SEE SEC'S SHALL BE |
| | SIZED PER 310.15B6 (MIN) AND SHALL BE |
| | SHOWN ON PLANS. |
| | PLEASE SEE 1-SET OF 2/0'S ARE SHOWN |
| | WHICH WAS FOR OLD 200A SERVICE. PLEASE |
| | SEE A MIN OF PARALLEL OR 400MCM IS |
| | REQUIRED. |
| | |
| | E)PLEASE SEE MIN GROUNDING ELECTRODE |
| | CONDUCTOR SHALL NOW BE SIZED PER 250.66 |
| | AS SEC'S AND SERVICE IS NOW CHANGED TO |
| | 400A'S ETC. |
| | |
| | F)PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| | MISSING PANELS. |
| | |
| | G)PLEASE SEE PANEL "A" IS SHOWN AS MLO, |
| | WHEN THIS IS ALSO SHOWN AS MCB ON |
| | RISER?? |
| | |
| | ABOVE PER 215.5 |
| | |
| | 2)NOTE: PLEASE SEE MISSING SD ON PLANS |
| | PER NFPA-72 11.5.1.1,OUTSIDE BEDRM 2ND |
| | FLR. |
| | PLEASE ALSO SEE SD IN MASTER BEDRM SHALL |
| | BE LOCATED A MIN OF 3' FROM THE PEAK OF |
| | A VAULTED CEILING. |
| | 11.8.3.5 |
| | |
| | 3)NOTE: PLEASE SEE MIN CLEARENCE PER |
| | 110.26 FOR CU#1 |
| | |
| | PLEASE REVISE AND CORRELATE THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | |