| Plan Review Notes For Permit 05010021 |
| Permit Number |
05010021 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-01 00:00:00 | ******** PROVISO/ NOTES REDLINED **** | | | | | | | | | 1)NOTE: PLEASE CORRELATE ELECTRICAL | | | PLANS WITH MECHANICALFOR AHU HEAT | | | STRIPS. | | | PLEASE SEE MECHANICAL PLANS INDICATE : | | | ONE 10KW AND TWO 7.5KW UNITS. | | | ELECTRICAL PLANS INDICATE ONE 10KW , ONE | | | 5KW AND ONE 6KW. | | | PLEASE SEE LOAD CALCULATIONS FOR THIS | | | WILL ALSO NEED TO BE ADJUSTED. | | | IF LARGER OF THE UNITS ARE INSTALLED, A | | | 200A SERVICE IS STILL OK. | | | | | | 2)NOTE: PLEASE SEE DISCONNECT'S FOR | | | AHU'S AND CU REDLINED PER 110.26. TO BE | | | FIELD VERIFIED. | | | | | | PLEASE SUBMIT REVISED PLANS FOR NOTE #1 | | | ALONG WITH ANY OTHER POSSIBLE REVISIONS | | | BEFORE ELECTRICAL ROUGH INSPECTION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|