Plan Review Notes
Plan Review Notes For Permit 05010021
Permit Number 05010021
Review Stop E
Sequence Number 2
Notes
Date Text
2005-03-01 00:00:00******** PROVISO/ NOTES REDLINED ****
  
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS WITH MECHANICALFOR AHU HEAT
 STRIPS.
 PLEASE SEE MECHANICAL PLANS INDICATE :
 ONE 10KW AND TWO 7.5KW UNITS.
 ELECTRICAL PLANS INDICATE ONE 10KW , ONE
 5KW AND ONE 6KW.
 PLEASE SEE LOAD CALCULATIONS FOR THIS
 WILL ALSO NEED TO BE ADJUSTED.
 IF LARGER OF THE UNITS ARE INSTALLED, A
 200A SERVICE IS STILL OK.
  
 2)NOTE: PLEASE SEE DISCONNECT'S FOR
 AHU'S AND CU REDLINED PER 110.26. TO BE
 FIELD VERIFIED.
  
 PLEASE SUBMIT REVISED PLANS FOR NOTE #1
 ALONG WITH ANY OTHER POSSIBLE REVISIONS
 BEFORE ELECTRICAL ROUGH INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  