| Plan Review Notes For Permit 05010021 |
| Permit Number |
05010021 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-20 00:00:00 | 1. RETURN AIR DUCT FOR A.H.U. #1 | | | SHOULD BE EQUEAL TO SUPPLY AIR DUCT | | | CONBINE , 314 SQ. IN. TO RETURN AIR DUCT | | | OF 201 SQ. IN. OF AREA. | | | RETURN AIR GRILL IS SOME WHAT SMALL | | | FOR THE SIZE OF A.H.U. . 2003 FBC/M | | | 601.4 . | | | 2. RETURN AIR DUCT OUT OF SECOND FLOOR | | | BEDROOMS SHOULD BE ONE AND HALF LARGER | | | THAN SUPPLY AIR DUCT.2003 FBC/M | | | EXCEPTION #1 . | | | 3.HALL WAY RETURN AIR GRILL MUST | | | COMPLY WITH 2003 FBC/M 601.4 EXCEPTION | | | #2 FOR SIZE. | | | 4. SUPPLY AIR DUCT LEADING TO BEDROOM | | | #3 AND #4 SHOULD BE LARGER THAN | | | REFLECTED ON PLAN. (4") | | | 5. CONDENSATE FROM A.H.U. MUST CONFORM | | | WITH 2003 FBC/M 307.2.3 .FOR AUX. DRAIN | | | PANS. |
|