Plan Review Notes
Plan Review Notes For Permit 05010021
Permit Number 05010021
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-20 00:00:001. RETURN AIR DUCT FOR A.H.U. #1
 SHOULD BE EQUEAL TO SUPPLY AIR DUCT
 CONBINE , 314 SQ. IN. TO RETURN AIR DUCT
 OF 201 SQ. IN. OF AREA.
 RETURN AIR GRILL IS SOME WHAT SMALL
 FOR THE SIZE OF A.H.U. . 2003 FBC/M
 601.4 .
 2. RETURN AIR DUCT OUT OF SECOND FLOOR
 BEDROOMS SHOULD BE ONE AND HALF LARGER
 THAN SUPPLY AIR DUCT.2003 FBC/M
 EXCEPTION #1 .
 3.HALL WAY RETURN AIR GRILL MUST
 COMPLY WITH 2003 FBC/M 601.4 EXCEPTION
 #2 FOR SIZE.
 4. SUPPLY AIR DUCT LEADING TO BEDROOM
 #3 AND #4 SHOULD BE LARGER THAN
 REFLECTED ON PLAN. (4")
 5. CONDENSATE FROM A.H.U. MUST CONFORM
 WITH 2003 FBC/M 307.2.3 .FOR AUX. DRAIN
 PANS.