| 2005-01-14 00:00:00 | ************* UNSAT **************** |
| | |
| | 1)NOTE; PLEASE CLARIFY SERVICE. SHOWN AS |
| | 400A METER MAIN COMBO , YET IT SEEMS |
| | SERVICE ONLY FEEDS A 200A DISC AND THEN |
| | PANEL? PLEASE ALSO SEE SEC'S ARE ONLY |
| | SHOWN AS 2/0'S FOR A 200A RATED |
| | SERVICE? |
| | IF INDEED A METER MAIN , PLEASE INCLUDE |
| | ANY BRKRS AND /OR BRKRS IN MM. |
| | IF INDEED 400A, PLEASE SEE 310.15B6 |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE 210.52 FOR SOME |
| | MISSING RECEPTS REQUIRED. |
| | |
| | 3)NOTE: PLEASE SEE GARAGE DOOR OPENERS |
| | EACH SHOWN ON 2-P 30A BRKRS? |
| | MISPRINT? |
| | |
| | 4)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN |
| | COUNTERSPACE RECEPTS MISSING. |
| | 210.8A6 |
| | |
| | 5)NOTE: PLEASE ADD SD IN HALL OUTSIDE |
| | BEDRM AS DOOR BETWEEN BEDRM AND OUTER |
| | HALL BLOCKS PROTECTION. |
| | NFPA-72 |
| | |
| | 6)NOTE: PLEASE SEE IF 400A SERVICE, THEN |
| | SIZE GROUNDING ELECTRODE CONDUCTOR PER |
| | 250.66. 1/0 MIN |
| | |
| | PLEASE SEE ONE SET OF PLANS HAS MOST OF |
| | THESE THINGS REDLINED FOR AREAS OF |
| | CONCERN. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |