| Plan Review Notes For Permit 04121980 |
| Permit Number |
04121980 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-11-14 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | | 1- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR WINDOW MULLIONS THAT MEET | | | THE DESIGN PRESSURES CALCULATED BY THE | | | ARCHITECT. WINDOW MULLION PRODUCT | | | APPROVAL SUBMITTED DON'T RESIST THE | | | DESIGN PRESSURES CALCULATED IN PLANS. | | | | | | 2- STORM SHUTTERS INFORMATION WAS | | | SUBMITTED ON 8-12-05. IT WAS REJECTED | | | BECAUSE IT WAS A REVISION AND | | | INFORMATION WAS NOT COMPLETE. SEE COPY | | | OF COMMENTS DATED 9-20-05. RESUBMIT AND | | | PAY REVISION FEES AS REQUIRED. | | | | | | NOTE: | | | REVISED SHEET A-6 AND STEEL HEADER | | | DETAIL ARE APPROVED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|