| Plan Review Notes For Permit 04121980 |
| Permit Number |
04121980 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-02 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- DESIGNER OF RECORD TO SPECIFY ON | | | PLANS ROOF TILE FASTENING AS REQUIRED BY | | | SEC. 104.2.1.1 CITY AMENDMENTS TO FBC. | | | 2- ANCHOR SCHEDULE: A)REVISE FASTENERS | | | FOR THD210 CONNECTOR. SEE TECHNICAL | | | BULLETIN. | | | B) CONNECTOR G: PROVIDE TESTING AND | | | ENGINEERING CALCS FOR NUMBER/TYPE OF | | | NAILS THAT DIFFER TO THOSE TESTED AND | | | PUBLISHED BY THE MANUFACTURER. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | **NAIL CALCS SHOWN ON SHEET A-6 ARE FOR | | | 10D NAILS ONLY. THEY DON'T APPLY TO 16D. | | | WHAT CRITERIA IS USED WHEN REDUCING THE | | | NUMBER OF NAILS. EG: SEE PAGE 17 OF USP | | | BOOK FOR LOADS REDUCTION (SIMPSON HAS AN | | | EQUATION ON PAGE 137 OF 2005 CATALOGUE). | | | 3- SPECIFY SIZE AND ANCHORS FOR WINDOW | | | MULLIONS AT LIVING ROOM FIXED WINDOWS TO | | | VERIFY DESIGN PRESSURES COMPLIANCE. SEE | | | PRODUCT APPROVAL FOR SIZE LIMITATIONS. | | | 4-STORM SHUTTERS: REVISE KEY PLAN AND | | | INSTALLATION SCHEDULE TO MATCH FLOOR | | | PLAN AND RE-SUBMIT. |
|