| Plan Review Notes For Permit 04121980 |
| Permit Number |
04121980 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A-7 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS: | | | A. THE FUTURE SINK ON THE PATIO DOES | | | NOT SHOW THE STUB OUT ABOVE THE SLAB, | | | SHOULD SHOW A RISER. ALSO THE SINK DOES | | | NOT SHOW A VENT. SECTIONS 104.2.1. & | | | 901.2.1. | | | B. DOUBLE SANITARY TEE PATTERNS SHALL | | | NOT RECIEVE THE DISCHARGE OF APPLIANCES | | | WITH PUMPING ACTION DISCHARGE. THE WASH | | | MACHINE SHALL CONNECT DOWNSTREAM OF THE | | | LAUNDRY SINK. SECTION 706.3 | | | C. THE CLEANOUT ON THE WASH MACHINE | | | STACK SHALL BE A MINIMUM OF 4' ABOVE THE | | | FLOOR FOR ACCESS. SECTION 708.10. | | | D. SEE RED LINE EXAMPLES OF CORRECT | | | PIPING/VENT/CLEANOUT ON A-7 SHEET. | | | 2) AS REQUIRED BY 104.3.1.1 OF THE CODE, | | | TWO OR MORE COPIES OF DRAWINGS ARE | | | REQUIRED. LOOSE SHEETS ARE NOT APPROVED, | | | PLEASE STAPLE SETS OF PLANS TOGETHER. | | | SECTIONS 104.2.1 & 104.2.1.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|