Plan Review Notes
Plan Review Notes For Permit 04121980
Permit Number 04121980
Review Stop P
Sequence Number 2
Notes
Date Text
2005-05-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-7 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS:
 A. THE FUTURE SINK ON THE PATIO DOES
 NOT SHOW THE STUB OUT ABOVE THE SLAB,
 SHOULD SHOW A RISER. ALSO THE SINK DOES
 NOT SHOW A VENT. SECTIONS 104.2.1. &
 901.2.1.
 B. DOUBLE SANITARY TEE PATTERNS SHALL
 NOT RECIEVE THE DISCHARGE OF APPLIANCES
 WITH PUMPING ACTION DISCHARGE. THE WASH
 MACHINE SHALL CONNECT DOWNSTREAM OF THE
 LAUNDRY SINK. SECTION 706.3
 C. THE CLEANOUT ON THE WASH MACHINE
 STACK SHALL BE A MINIMUM OF 4' ABOVE THE
 FLOOR FOR ACCESS. SECTION 708.10.
 D. SEE RED LINE EXAMPLES OF CORRECT
 PIPING/VENT/CLEANOUT ON A-7 SHEET.
 2) AS REQUIRED BY 104.3.1.1 OF THE CODE,
 TWO OR MORE COPIES OF DRAWINGS ARE
 REQUIRED. LOOSE SHEETS ARE NOT APPROVED,
 PLEASE STAPLE SETS OF PLANS TOGETHER.
 SECTIONS 104.2.1 & 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]