| 2005-05-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENING AS REQUIRED BY SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 2-UPDATE TRUSS ANCHOR SCHEDULE. SEE |
| | LATEST CATALOGUE THAT WAS REVISED TO |
| | COMPLY WITH SECTION 1609.4.3 FBC 2001. |
| | OTHERWISE, PROVIDE COMPLETE ENGINEERING |
| | CALCS FOR FASTENER TYPE AND NUMBER THAT |
| | DIFFER FROM THOSE TESTED AND PUBLISHED |
| | BY THE MANUFACTURER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 3- ELEVATIONS CALL FOR FLAT TILE. |
| | PRODUCT APPROVAL SUBMITTED WAS FOR "S" |
| | TILE. REVISE AS REQUIRED. |
| | |
| | 4- INSURANCE WILL EXPIRE ON 5-27-05. |
| | PLEASE, UPDATE INFORMATION AT TIME OF |
| | SUBMITTAL TO AVOID ANY DELAYS. |
| | |
| | 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR FRENCH DOORS WITH |
| | SIDELITES. PRODUCT SUBMITTED ARE FOR |
| | 6'-8" DOORS. NEED 8'-0" HEIGHT DOORS. |
| | |
| | 6- OWES $949.68 FOR UPDATE VALUE AND |
| | RADON FEES. AND, FOR ADDED A/C AREA. |
| | |
| | 7- DETAIL 2/A-9:PROVIDE SPECS FOR "U" |
| | STRAP TO BE USED. SEC. 104.2.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 8- DESIGN PARAMETERS ON SHEET A-3: |
| | SPECIFY/CLARIFY WHERE IS THE BASIC |
| | VELOCITY PRESSURE TAKEN FROM?. THERE ARE |
| | NOT TABLES ON CHAPTER 16 FBC 2001 |
| | SHOWING THIS VALUES. |
| | |
| | 9- LEFT SIDE ELEVATION DON'T MATCH FLOOR |
| | PLAN. NEED TO SHOW MASTER BEDROOM |
| | SITTING AREA. REVISE AS REQUIRED. |
| | |
| | 10- REVISE FRONT ELEVATION TO SHOW STEEL |
| | DOOR AS PER PRODUCT APPROVAL SUBMITTED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |
| | |