Plan Review Notes
Plan Review Notes For Permit 04121974
Permit Number 04121974
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-14 00:00:00REDLINED:
 POSSIBLE RECEPT FOR BEDRM #2, 210.52
 CONTINUOUS LOAD (125%) FOR POOL PUMP.
 REDLINED GROUNDING ELECTRODE CONDUCTOR
 TO BE A MIN OF 1/0. 250.66,310.15B6
  
 NO NEED FOR CORRECTIONS, OR REVISIONS,
 HOWEVER IF PLANS COME BACK IN WITH ANY
 OTHER REVISIONS, PLEASE ADJUST AT THAT
 TIME.
  
  
  
 **PLANS ROUTED TO PLUMB, AS NEW PLUMBING
 SHEETS WERE IN SETS.