| Plan Review Notes For Permit 04121974 |
| Permit Number |
04121974 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-07-14 00:00:00 | REDLINED: | | | POSSIBLE RECEPT FOR BEDRM #2, 210.52 | | | CONTINUOUS LOAD (125%) FOR POOL PUMP. | | | REDLINED GROUNDING ELECTRODE CONDUCTOR | | | TO BE A MIN OF 1/0. 250.66,310.15B6 | | | | | | NO NEED FOR CORRECTIONS, OR REVISIONS, | | | HOWEVER IF PLANS COME BACK IN WITH ANY | | | OTHER REVISIONS, PLEASE ADJUST AT THAT | | | TIME. | | | | | | | | | | | | **PLANS ROUTED TO PLUMB, AS NEW PLUMBING | | | SHEETS WERE IN SETS. |
|