| Plan Review Notes For Permit 04121968 |
| Permit Number |
04121968 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-11-16 00:00:00 | *** REDLINED *** | | | | | | 1)A/C OCP SHALL BE SIZED PER | | | MANUFACTURE. | | | 5KW HEAT SHOWN FOR A/C#2 AND #3, YET | | | PANEL SCHEDULE INDICATES 60A AND #6. | | | | | | 2)PLEASE ALSO SEE MAIN SERVICE IS NOW | | | SHOWN AS 400A'S. PLEASE SEE MIN SIZE GEC | | | SHALL BE SIZED PER 250.666, 310.15B6 | | | 1/0 MIN. | | | |
|