Plan Review Notes For Permit 04121962
Permit Number 04121962
Review Stop B
Sequence Number 4
Notes
Date Text
2005-09-02 00:00:00STORM PANEL REVISION DENIED
  
 1) SPECIFY THE ANCHOR TYPE, CONNECTION
 TYPE AND EDGE DISTANCE AS REQUIRED BY
 THE PRODUCT APPROVAL ANCHOR SCHEDULE TO
 DETERMINE ANCHOR SPACING.
  
 2) ON SHEET 4 OF THE PRODUCT APPROVAL,
 THE MAXIMUM DESIGN PRESSURE FOR A PANEL
 SPAN OF 129" IS 39.10 PSF AND ON THE
 INSTALLATION SCHEDULE SUBMITTED, THE
 PRESSURE AT OPENING #6 FOR THE 129"
 SHUTTER SPAN IS 43 PSF. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  