| Plan Review Notes For Permit 04121962 |
| Permit Number |
04121962 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-09-02 00:00:00 | STORM PANEL REVISION DENIED | | | | | | 1) SPECIFY THE ANCHOR TYPE, CONNECTION | | | TYPE AND EDGE DISTANCE AS REQUIRED BY | | | THE PRODUCT APPROVAL ANCHOR SCHEDULE TO | | | DETERMINE ANCHOR SPACING. | | | | | | 2) ON SHEET 4 OF THE PRODUCT APPROVAL, | | | THE MAXIMUM DESIGN PRESSURE FOR A PANEL | | | SPAN OF 129" IS 39.10 PSF AND ON THE | | | INSTALLATION SCHEDULE SUBMITTED, THE | | | PRESSURE AT OPENING #6 FOR THE 129" | | | SHUTTER SPAN IS 43 PSF. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|