| Plan Review Notes For Permit 04121956 |
| Permit Number |
04121956 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-09 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- SHUTTERS UNDER A SEPARATE PERMIT. | | | 2- DESIGNER OF RECORD (NOT THE BUILDER) | | | TO SPECIFY ROOF TILE FASTENING. SEC. | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | 3- A) REVISE FASTENERS SPECIFIED FOR | | | THD210. SEE TECHNICAL BULLETIN & PROVIDE | | | CORRESPONDING PRODUCT APPROVAL. | | | 4- CLARIFY IF USING CASEMENT WINDOW WITH | | | IMPACT GLASS OR NOT & PROVIDE | | | CORRESPONDING PRODUCT APPROVAL. | | | 5- A) PROVIDE FLORIDA/LOCAL PRODUCT | | | APPROVAL FOR 5"X5"X1/4" STRUCTURAL | | | MULLION SPECIFIED ON ARCHITECT'S DETAIL. | | | B) PROVIDE FLORIDA/LOCAL PRODUCT | | | APPROVAL FOR OTHER MULLIONS TO BE USED. | | | AND SPECIFY MULLION SIZE AND ANCHORS FOR | | | FIXED WINDOWS IN LIVING ROOM AREA. | | | 6- PROVIDE COMPLETE APPROVED LISTING AND | | | SPECS FOR BBQ AND EXHAUST HOOD FOR PORCH | | | INSTALLATION.SECTION 2808 FBC 2001. |
|