2005-06-07 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 2- USP CONNECTOR THD210 OR THD210-2 IS A
 WOOD TO WOOD CONNECTOR. NEED TO SPECIFY
 MASONRY CONNECTOR. SEE CATALOGUE FOR
 PROPER MASONRY CONNECTOR. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3- STORM SHUTTERS: NEED TO REVISE THE
 MIN. PANEL SPAN ACCORDING TO THE
 ENGINEERED DRAWINGS MOUNTING CONDITION
 SELECTED. SEE DRAWINGS AND REVISE AS
 REQUIRED.
  
 4- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DON'T MATCH NOA'S
 SUBMITTED FOR THE FLORIDA PRODUCT
 APPROVAL. RESUBMIT CORRECT NOA.
  
 5- WINDOW/DOOR MULLION PRODUCT APPROVAL
 SUBMITTED DOESN'T RESIST DESIGN
 PRESSURES CALCULATED ON DRAWINGS.
 PROVIDE PRODUCT APPROVAL FOR MULLIONS
 THAT MEET SUCH PRESSURES. CLEARLY
 SPECIFY SIZE AND ANCHOR TYPE. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 6- BBQ INFORMATION SUBMITTED TO BE
 REVIEWED BY BUILDING OFFICIALFOR
 APPROVAL.
 NOTE: THERE ARE SOME BBQ'S THAT ARE
 SPECIFICALLY DESIGNED TO BE INSTALLED IN
 THE PORCH OR LANAI. THEY REQUIRE THE
 EXHAUST HOOD. BUILDING OFFICIAL MAY
 REQUIRE ADDITIONAL INFORMATION OR
 TESTING TO SUPPORT ALFRESCO GRILLS'S
 LETTER STATING THAT HOOD IS NOT REQ'D.
  
 7- SHEET A-6: REVISE TYPO ON ROOF
 DIAPHRAGM. IT SHOULD READ 4' NOT 4".
  
 8- SHEET A-3: CLARIFY WHERE IS THE BASIC
 VELOCITY PRESSURE TAKEN FROM? THIS WAS
 PART OF THE STANDARD BUILDING CODE NOT
 THE FLORIDA BUILDING CODE.
  