2005-01-27 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SECTION 11-11 FBC 2001.
  
 2- SPECIFY ROOF TILE FASTENING. SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE TRUSS ANCHOR SCHEDULE.
 PROVIDE
 COMPLETE ENGINEERING CALCS FOR TYPE AND
 NUMBER OF FASTENERS THAT DIFFER FROM
 THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 4- A) PLANS NEED THE NAME OF ARCHITECT
 SEALING THE PLANS. CHAPTER 61G1-16004.
 B) STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5- PROVIDE COMPLETE DETAIL/SPECS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES. SPECIFY FASTENERS AND SPACING.
 SEE ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
  
 6- OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS.
  
 7- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS. SEE SIZE ON PLANS.
 B) FRENCH DOORS. SEE SIZES ON PLANS.
 C) CONCRETE LINTELS: PROVIDE DADE
 COUNTY
 NOA THAT MATCHES ONE SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 D) FIXED WINDOWS THAT MEET THE DESIGN
 PRESSURES SHOWN ON PLANS. SEE PLANS FOR
 SIZES AND DESIGN PRESSURES.
 E) ARABESQUE WINDOW. SEE PLANS.
  
 8- A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR FIREPLACE. SEC. 2806 FBC
 2001.
 B) PROVIDE COMPLETE APPROVED BBQ SPECS.
 SECTION 2808 FBC 2001.
  
 9- STORM SHUTTERS: A) KEY PLAN DOESN'T
 MATCH PLANS. REVISE AS REQUIRED.
 B) REVISE MIN. PANEL SIZE. SEE
 LIMITATIONS ON ENGINEERED DRAWINGS.
 C) REVISE END AND INTERIOR ZONES. SEE
 PLANS FOR LOCATION.
 D) REVISE OPENINGS DESIGN PRESSURES.
 SEE
 PLANS.
  
 10- PROVIDE COMPLETE FRAMING DETAILS
 FOR
 ARABESQUE WINDOW. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11- OWES $866.23 FOR UPDATED VALUATION.
  
 12- REVISE FOUNDATION NOTE #2 ON SHEET
 A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
  
 13- REVISE CONNECTORS SPECIFIED ON
 DETAIL 2/A-9. "SEMCO" IS OUT OF
 BUSINESS.
  