| Plan Review Notes For Permit 04121950 |
| Permit Number |
04121950 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-22 00:00:00 | ********** PROVISO ************ | | | | | | 1)NOTE: PLEASE SEE AHU'S AND CU'S ON | | | PANEL SCHEDULES AND LOAD CALCULATIONS. | | | PLEASE CORRELATE OCP, AWG AND KW LOADS | | | FOR EACH. | | | PLEASE ADJUST LOAD CALCULATIONS AS | | | NEEDED. | | | | | | 2)NOTE: PLEASE SEE 110.26 FOR MIN | | | CLEARENCE REQUIRED FOR POOL PANEL. | | | | | | 3)NOTE: PLEASE SEE DISH/DISP IS SHOWN AS | | | 2-P, HOWEVER ONLY INDICATES ONE CIRCUIT | | | SPACE ON PANEL SCHEDULE. | | | | | | 4)NOTE: PLEASE SEE RISER INDICATES 2/0'S | | | FOR 150A MAINS, THIS IS OK, HOWEVER IF | | | 2/0'S ARE SHOWN THEN THIS IS WHAT WILL | | | BE REQUIRED TO BE INSTALLED. | | | ***THIS IS ONLY A NOTE*** | | | | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW ALONG | | | WITH ANY OTHER REVISIONS BEFORE FINAL | | | ELECTRICAL INSPECTION IS CALLED IN. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|