| Plan Review Notes For Permit 04121944 |
| Permit Number |
04121944 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-04-29 00:00:00 | BUILDING REVIEW PROVISO: | | | PROVIDE INFORMATION PRIOR TO | | | CONSTRUCTION OR INSTALLATION TO AVOID | | | DELAYS OR CONFLICTS. | | | | | | 1- PROVIDE COMPLETE STORM SHUTTERS | | | INFORMATION UNDER ANOTHER PERMIT AS | | | AGREED UPON WITH CONTRACTOR. | | | | | | 2- DESIGNER OF RECORD TO SPECIFY ROOF | | | TILE FASTENING AS REQUIRED BY SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | 3- UPDATE/REVISE TRUSS ANCHOR SCHEDULE. | | | PROVIDE COMPLETE ENGINEERING CALCS FOR | | | TYPE AND NUMBER OF FASTENERS THAT DIFFER | | | FROM MANUFACTURER'SCATALOGUE. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | | | 4- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR FRENCH DOORS WITH SIDELITES | | | AS SHOWN ON PLANS. | | | | | | 5- DESIGN PARAMETERS CRITERIA: CLARIFY | | | WHERE IS THE BASIC VELOCITY PRESSURE | | | TAKEN FROM. IT'S NOT SHOWN ON CHAPTER 16 | | | FBC 2001. SEC. 104.2.1.2 CITY AMENDMENTS | | | TO FBC 2001. | | | |
|