Plan Review Notes
Plan Review Notes For Permit 04121944
Permit Number 04121944
Review Stop B
Sequence Number 2
Notes
Date Text
2005-03-28 00:00:00CHECKLIST:
 1- SPECIFY ROOF TILE FASTENING. THIS IS
 THE DESIGNER OF RECORD RESPONSIBILITY,
 NOT THE BUILDER. SEE SEC. 104.2.1.1.
 CITY AMENDMENTS TO FBC 2001.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE. PROVIDE COMPLETE
 ENGINEERING CALCS FOR TYPE AND NUMBER OF
 FASTENERS THAT DIFFER FROM THOSE TESTED
 AND PUBLISHED BY MANUFACTURER.
 **NOTE: CALCULATIONS TO COMPLY WITH SEC.
 1609.4.3 FBC 2001.
  
 3- STORM SHUTTERS INFORMATION WAS NOT
 CHANGED FROM PREVIOUS CHECKLIST:
 A) NEED ENGINEER'S ORIGINAL SEAL,
 SIGNATURE AND DATE AS REQUIRED BY
 GENERAL NOTE #6.
 B) KEY PLAN DOESN'T MATCH PLANS.
 C) CLEARLY INDICATE ON DWGS INSTALLATION
 SCHEDULESPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO (MASONRY
 OR CONCRETE).
  
 4- ENERGY CALCULATIONS: A) A/C AREA
 DOESN'T MATCH PLANS. THESE PLANS INCLUDE
 ADDITIONAL SITTING AREA.
 B) COMPLETE ALL INFORMATION ON TOP OF
 FORM. INCLUDING PROJECT ADDRESS, ETC.
  
 5- CLARIFY IF USING FLUSH STEEL DOOR AT
 ENTRY. ARCHITECT'S ELEVATION SHOW GLASS
 DOORS. PROVIDE PRODUCT APPROVAL THAT
 MATCHES DOOR.
  
 6- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS. NEED RE-RECORDED N.O.C.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.