| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE OVERCURRENT PROTECTION FOR AHU |
| | #2& #3 AT 60 AMPS IS TOO LARGE TO |
| | PROTECTA 5KW UNIT.(5000X125%/240=26 |
| | AMPS, MAX30 AMP OCP). ALSO 60 AMP OCP |
| | SHOWN IN THE MAIN PANEL SEEMS TOO LARGE |
| | FOR THE CONDENSING UNITS. SEE ARTICLE |
| | 440.22 NEC. |
| | |
| | 2} THERE ARE ONLY TWO A/C DISCONNECTS |
| | SHOWN ON THE RISER, BUT THREE UNITS ON |
| | THE PLAN AND IN THE CALC. PLEASE |
| | CORRELATE. |
| | |
| | 3} THERE ARE NO PROVISIONS IN THE |
| | CALCULATIONS FOR POOL EQUIPMENT, BUT |
| | THERE IS EQUIPMENT SHOWN ON THE PLAN. |
| | |
| | 4} IF NOTE #14 IS ADHERED TO, THOSE |
| | CIRCUITS WOULD HAVE TO BE PROTECTED BY |
| | AN AFCI BECAUSE THE DETECTORS ARE |
| | LOCATED IN BEDROOMS. 210.12. |
| | |
| | 5} THE GFI'S SHOWN IN THE DINING ROOM |
| | AND BREAKFAST NOOK, WHILE NOT REQUIRED |
| | ALTHOUGH PERMISSIBLE, MUST BE INSTALLED |
| | IF LEFT ON THE PLAN. |
| | |
| | 6} RECEPTACLES MUST BE ADDED TO THE |
| | MASTER SUITE AND HOBBY ROOM TO COMPLY |
| | WITH 210.52(A). SEE REVIEWED SET OF |
| | PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |