2005-01-24 00:00:00DENIED
  
 1) SPECIFY ON SHEET A3 THAT THE GLASS
 BLOCK ON THE ZERO LOT LINE IS ONE HOUR
 FIRE RATED.
  
 2) ONE OF THE WINDOWS IN BEDROOM #3
 SPECIFIED AS AN EGRESS WINDOW IS MARKED
 AS A H33 SH, WHICH DOES NOT MEET EGRESS
 REQUIREMENTS.
  
 3) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE BBQ AND THE
 PREFAB FIREPLACE.
  
 4) FBC 1007.8.1 REQUIRES STAIR WINDERS
 TO HAVE A MINIMUM TREAD DEPTH OF 6" AT
 THE NARROW EDGE AND A MINIMUM TRED DEPTH
 OF 11" AT A POINT 12" FROM THE NARROW
 EDGE.
  
 5) PROVIDE DETAILS OF THE HANDRAILS AND
 GUARDRAILS AT THE STAIRS. SEE FBC 1007.5
 AND 1015.
  
 6) SPECIFY THE WINDLOAD PRESSURES FOR
 THE 7' X 5' FIXED GLASS WINDOW AT THE
 BREAKFAST NOOK.
  
 7) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 ANCHOR BOLTS IN DETAIL 6 ON A7.
  
 8) THE DETAIL FOR THE WOOD FRAME WALL ON
 A8 SPECIFIES A USP RT16F AT THE BOTTOM
 OF THE WALL AND DETAIL 7 ON A12
 SPECIFIES A USP RT18F AT THIS LOCATION.
 PLEASE CLARIFY.
  
 9) THE GLASS BLOCK DETAIL ON A12
 INCORRECTLY REFERENCES ASCE 7-88. THE
 CORRECT REFERENCE IS ASCE 7-98.
  
 10) SECTIONS 1 AND 2 ON A13 SPECIFY
 FIRESTOPS AT 8 INCHES ON CENTER. PLEASE
 CORRECT.
  
 11) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORMS PER FBC CHAPTER
 13.
  
 12) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK. THE PRODUCT
 APPROVAL SUBMITTED FOR THE GLASS BLOCK
 IS FOR SILICONE SET AND MAY NOT PROVIDE
 THE REQUIRED FIRE RATING OBTAINED WITH
 MORTAR SET. REFER TO SPECS.
  
 13) SUBMIT TWO COPIES OF STATE PRODUCT
 APPROVAL FOR THE LARGE OVERHEAD GARAGE
 DOOR.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE
 DOUBLE OUTSWING GLAZED WOOD ENTRY
 DOORS.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE OUTSWING GLAZED FRENCH DOOR AT
 THE MASTER SUITE.
  
 16)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 17) THE PRODUCT APPROVALS SUBMITTED FOR
 THE MULLIONS DO NOT MEET THE REQUIRED
 PRESSURES FOR USE BETWEEN THE 12'
 SLIDING GLASS DOOR AND TRANSOM AT THE
 FAMILY ROOM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714