Plan Review Notes
Plan Review Notes For Permit 04121932
Permit Number 04121932
Review Stop B
Sequence Number 5
Notes
Date Text
2005-08-30 00:00:00STORM PANEL RVISION IS DENIED.
  
 1) SPECIFY THE ANCHOR TYPE, CONNECTION
 TYPE AND EDGE DISTANCE AS REQUIRED BY
 THE PRODUCT APPROVAL ANCHOR SCHEDULE TO
 DETERMINE ANCHOR SPACING.
  
 2) ON SHEET 4 OF THE PRODUCT APPROVAL
 THE MAXIMUM DESIGN PRESSURE FOR A PANEL
 SPAN OF 129" IS 39.10 PSF AND ON THE
 INSTALLATION SCHEDULE SUBMITTED THE
 PRESSURE AT OPENING #10 FOR THE 129"
 SHUTTER SPAN IS 43 PSF. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved