Plan Review Notes
Plan Review Notes For Permit 04121932
Permit Number 04121932
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-18 00:00:00DENIED
  
 1) NO OPENINGS ARE ALLOWED IN THE WALL
 ON THE ZERO LOT LINE PER FBC TABLE 600.
 REMOVE THE GARAGE VENT ON THE ZERO LOT
 LINE.
  
 2) SPECIFY ONE HOUR FIRE RATED GLASS
 BLOCK AT THE ZERO LOT LINE ON THE FLOOR
 PLAN.
  
 3) THE GLASS BLOCK DETAIL ON A9
 INCORRECTLY REFERENCES ASCE 7-88. THE
 CORRECT REFERENCE IS ASCE 7-98.
  
 4) CHAPTER 11 OF THE 2001 FBC REQUIRES
 AT LEAST ONE FULL BATHROOM WITH A DOOR
 THAT HAS A 29" CLEAR OPENING.
  
 5) THE DETAIL 2 ON A9 SPECIFIES
 "SEMCO"CONNECTORS. SEMCO IS NO LONGER IN
 BUSINESS AND DOES NOT HAVE STATE PRODUCT
 APPROVAL.
  
 6) SPECIFY THE POSITIVE AND NEGATIVE
 DESIGN PRESSURES FOR THE SMALL GARAGE
 DOOR AND THE 8' WIDE SLIDING GLASS DOOR.
  
  
 7) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALCULATION FORM PER FBC
 CHAPTER 13.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BBQ AND
 PREFAB FIREPLACE.
  
 9) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS HAS AN
 EXTRA WINDOW THAT IS NOT SHOWN ON THE
 PLANS. THE SINGLE FRENCH DOOR IS SHOWN
 AS A DOUBLE DOOR ON THE KEY PLAN.
  
 10) SUBMIT STATE/LOCAL PRODUCT APPROVAL
 FOR THE SINGLE OUTSWING GLAZED FRENCH
 DOOR AND THE DOUBLE OUTSWING WOOD ENTRY
 DOORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714