| Date |
Text |
| 2005-01-18 00:00:00 | DENIED |
| | |
| | 1) NO OPENINGS ARE ALLOWED IN THE WALL |
| | ON THE ZERO LOT LINE PER FBC TABLE 600. |
| | REMOVE THE GARAGE VENT ON THE ZERO LOT |
| | LINE. |
| | |
| | 2) SPECIFY ONE HOUR FIRE RATED GLASS |
| | BLOCK AT THE ZERO LOT LINE ON THE FLOOR |
| | PLAN. |
| | |
| | 3) THE GLASS BLOCK DETAIL ON A9 |
| | INCORRECTLY REFERENCES ASCE 7-88. THE |
| | CORRECT REFERENCE IS ASCE 7-98. |
| | |
| | 4) CHAPTER 11 OF THE 2001 FBC REQUIRES |
| | AT LEAST ONE FULL BATHROOM WITH A DOOR |
| | THAT HAS A 29" CLEAR OPENING. |
| | |
| | 5) THE DETAIL 2 ON A9 SPECIFIES |
| | "SEMCO"CONNECTORS. SEMCO IS NO LONGER IN |
| | BUSINESS AND DOES NOT HAVE STATE PRODUCT |
| | APPROVAL. |
| | |
| | 6) SPECIFY THE POSITIVE AND NEGATIVE |
| | DESIGN PRESSURES FOR THE SMALL GARAGE |
| | DOOR AND THE 8' WIDE SLIDING GLASS DOOR. |
| | |
| | |
| | 7) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALCULATION FORM PER FBC |
| | CHAPTER 13. |
| | |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND LISTING INFORMATION FOR THE BBQ AND |
| | PREFAB FIREPLACE. |
| | |
| | 9) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS HAS AN |
| | EXTRA WINDOW THAT IS NOT SHOWN ON THE |
| | PLANS. THE SINGLE FRENCH DOOR IS SHOWN |
| | AS A DOUBLE DOOR ON THE KEY PLAN. |
| | |
| | 10) SUBMIT STATE/LOCAL PRODUCT APPROVAL |
| | FOR THE SINGLE OUTSWING GLAZED FRENCH |
| | DOOR AND THE DOUBLE OUTSWING WOOD ENTRY |
| | DOORS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |