Plan Review Notes
Plan Review Notes For Permit 04121926
Permit Number 04121926
Review Stop E
Sequence Number 7
Notes
Date Text
2005-09-20 00:00:00******* UNSAT **********
  
 PLEASE SEE REVISIONS WILL BE COMING BACK
 FOR PLUMBING COMMENTS, PLEASE MAKE THE
 BELOW CORRECTIONS AT THIS TIME.
  
 1)NOTE: PLEASE SEE OCP FOR CON/A/C SYS
 #1 WAS INCREASED TO 60A'S, HOWEVER
 CONDUCTOR SIZE HAS NOT BEEN INCREASED.
 PLEASE SEE 310.16,240.4
  
 2)NOTE: PLEASE SEE DISHWASHER /DISPOSAL
 CIRCUIT HAS BEEN UPGRADED TO A 2-POLE
 BRKR, HOWEVER CIRCUITING ON PANEL
 SCHEDULE STILL SHOWS 1-POLE.
  
 3)NOTE;PLEASE SEE ITEMS ON PLANS WHICH
 INDICATE BEING "OPTIONAL". PLEASE REVISE
 TO INCLUDE ACTUAL INSTALLATION OF
 ELECTRICAL. IF AN APPLIANCE, THE
 APPLIANCE DOES NOT HAVE TO BE INSTALLED
 FOR ROUGH OR BEFORE FINAL.
 ONLY THE ELECTRICAL FOR THE EQUIPMENT IS
 TO BE SHOWN.
 PLEASE KNOW, ELECTRICAL FOR WASHER
 CIRCUIT CAN NOT BE OPTIONAL.
 210.52,210.11,220.16
  
 4)NOTE: PLEASE SEE LOCATION FOR POOL SUB
 PANEL SHOULD BE LOCATED TO MEET 110.26
 FOR MIN CLEARNECES.
 PLEASE SEE POOL EQUIPMENT WAS NOTED ON
 PREVIOUS PLANS AS TO BE MOVED TO EXACT
 LOCATION AT LATER DATE, HOWEVER THIS HAS
 NOTBEEN REVISED AS OF YET?
 110.26
  
 PLEASE SEE PLUMB COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717