| 2005-09-20 00:00:00 | ******* UNSAT ********** |
| | |
| | PLEASE SEE REVISIONS WILL BE COMING BACK |
| | FOR PLUMBING COMMENTS, PLEASE MAKE THE |
| | BELOW CORRECTIONS AT THIS TIME. |
| | |
| | 1)NOTE: PLEASE SEE OCP FOR CON/A/C SYS |
| | #1 WAS INCREASED TO 60A'S, HOWEVER |
| | CONDUCTOR SIZE HAS NOT BEEN INCREASED. |
| | PLEASE SEE 310.16,240.4 |
| | |
| | 2)NOTE: PLEASE SEE DISHWASHER /DISPOSAL |
| | CIRCUIT HAS BEEN UPGRADED TO A 2-POLE |
| | BRKR, HOWEVER CIRCUITING ON PANEL |
| | SCHEDULE STILL SHOWS 1-POLE. |
| | |
| | 3)NOTE;PLEASE SEE ITEMS ON PLANS WHICH |
| | INDICATE BEING "OPTIONAL". PLEASE REVISE |
| | TO INCLUDE ACTUAL INSTALLATION OF |
| | ELECTRICAL. IF AN APPLIANCE, THE |
| | APPLIANCE DOES NOT HAVE TO BE INSTALLED |
| | FOR ROUGH OR BEFORE FINAL. |
| | ONLY THE ELECTRICAL FOR THE EQUIPMENT IS |
| | TO BE SHOWN. |
| | PLEASE KNOW, ELECTRICAL FOR WASHER |
| | CIRCUIT CAN NOT BE OPTIONAL. |
| | 210.52,210.11,220.16 |
| | |
| | 4)NOTE: PLEASE SEE LOCATION FOR POOL SUB |
| | PANEL SHOULD BE LOCATED TO MEET 110.26 |
| | FOR MIN CLEARNECES. |
| | PLEASE SEE POOL EQUIPMENT WAS NOTED ON |
| | PREVIOUS PLANS AS TO BE MOVED TO EXACT |
| | LOCATION AT LATER DATE, HOWEVER THIS HAS |
| | NOTBEEN REVISED AS OF YET? |
| | 110.26 |
| | |
| | PLEASE SEE PLUMB COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |