| 2005-09-21 00:00:00 | BUILDING REVISION CHECKLIST: | | | 1- STORM SHUTTERS KEY PLAN DOESN'T MATCH | | | FLOOR PLANS. REVISE AS REQUIRED. | | | | | | 2- REVISE INSTALLATION SCHEDULE TO | | | PROVIDE MINIMUM REQUIRED INFORMATION. | | | SEE ATTACHED SAMPLE WHICH IS MORE | | | COMPLETE THAN THE ONE SUBMITTED. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | | | 3- CLEARLY MARK ON SHUTTER DRAWINGS | | | SPECIFIC MOUNTING CONDITIONS AND ANCHOR | | | TYPE AND SPACING TO BE USED ACCORDING TO | | | THE DESIGN PRESSURES, EDGE DISTANCE, | | | PANEL SPAN, CONNECTION TYPE AND | | | STRUCTURE TO BE ATTACHED TO (CONCRETE OR | | | CONCRETE BLOCK). SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 4- ACCORDING TO MAXIMUM PANEL SPAN CHART | | | ON DRAWINGS 4 OF 7 OPENING #12 EXCEEDS | | | THE MAXIMUM SPAN. REVISE AS REQUIRED. | | | SECTION 104.2.1.2 CITY AMENDMENTS TO FBC | | | 2001. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|