| 2005-01-21 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PROVIDE COMPLETE BATHROOM WITH A DOOR |
| | THAT ALLOWS 29" MIN. CLEAR OPENING AS |
| | REQUIRED BY SEC. 11-11 OF FBC 2001. |
| | |
| | 2-SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 104.2.1.1 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 3-UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE |
| | COMPLETE ENGINEERING CALCULATIONS FOR |
| | TYPE AND NUMBER OF FASTENERS THAT |
| | DIFFER |
| | FROM THOSE TESTED AND PUBLISHED ON |
| | MANUFACTURER'S CATALOGUE REFLECTING NO |
| | STRESS INCREASE AS REQUIRED BY SECTION |
| | 1609.4.3 FBC 2001. |
| | |
| | 4-TITLE BLOCK TO HAVE ALL INFORMATION |
| | AS |
| | REQUIRED BY CHAPTER 481 FLORIDA |
| | STATUTES |
| | AND CHAPTER 61G1-16.004 OF |
| | ADMINISTRATIVE CODE. INCLUDING NAME OF |
| | ARCHITECT SEALING THE PLANS. |
| | ***ALSO, STATE REGISTRATION NUMBER IS |
| | INCORRECT. REVISE AS REQUIRED. |
| | |
| | 5-PROVIDE COMPLETE |
| | DETAIL/SPECIFICATIONS |
| | FOR INSTALLATION OF CEILING AT ENTRY |
| | AND |
| | REAR PORCHES. SPECIFY FASTENERS TYPE |
| | AND |
| | SPACING AS REQUIRED BY ASTM C926 AND |
| | ASTM C1063. (SEC. 2504.2 FBC 2001.) |
| | |
| | 6-ENERGY CALCULATIONS: OWNER/AGENT TO |
| | SIGN AND DATE BOTTOM OF FORM. |
| | |
| | 7-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR ENTRY DOORS AND ALL |
| | EXTERIOR FRENCH DOORS. CHECK SIZES. |
| | |
| | 8-STORM SHUTTERS: A)KEY PLAN DON'T |
| | MATCH |
| | PLANS. |
| | B)SEE ENGINEERED DRAWINGS FOR MIN. |
| | PANEL |
| | SIZE ALLOWED AND REVISEINSTALLATION |
| | SCHEDULE AS REQUIRED.. |
| | C) INTERIORAND END ZONES SHOWN ON |
| | INSTALLATION SCHEUDLE ARE INCORRECT. |
| | SEE |
| | PLANS AND REVISE AS REQUIRED. |
| | D) REVISE DESIGN PRESSURES SHOWN ON THE |
| | INSTALLATION SCHEDULE. SEE PLANS.. |
| | |
| | 9-CONCRETE LINTELS PRODUCT APPROVAL: |
| | PROVIDE COPIES OF MIAMI-DADE NOA REPORT |
| | THAT WAS SUBMITTED FOR FLORIDA PRODUCT |
| | APPROVAL. REPORT SUBMITTED HERE IS NOT |
| | THE SAME. SEE INFORMATION ON FLORIDA |
| | WEBSITE WWW.FLORIDABUILDING.ORG. |
| | |
| | 10-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR FIXED WINDOWS THAT MEET |
| | THE |
| | DESIGN PRESSURES CALCULATED ON PLANS. |
| | |
| | 11-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR ARABESQUE WINDOW SHOWN ON |
| | FRONT ELEVATION. |
| | |
| | 12-PROVIDE COMPLETE FRAMING DETAILS FOR |
| | ARABESQUE WINDOW. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 13-OWES $235.45 FOR UPDATED VALUATION. |
| | |
| | 14-FOUNDATION NOTES ON SHEET A-2: REVISE |
| | NOTE #2. SEE CHAPTER 19 FBC 2001 FOR |
| | PROPER ACI REFERENCE. |
| | |
| | 15-DETAIL 2/A-9: UPDATE CONNECTORS. |
| | SEMCO IS OUT OF BUSINESS. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |
| 2005-01-05 00:00:00 | MUST PULL SEPERATE PERMIT FOR POOL/DECK |