| 2005-10-03 00:00:00 | REVISION CHECKLIST: |
| | 1- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR |
| | STORM SHUTTERS AS REQUIRED BY RULE 9B-72 |
| | OF DCA. DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATEWIDE PRODUCT |
| | APPROVAL. MANUFACTURER MAY APPLY FOR |
| | LOCAL PRODUCT APPROVAL USING THE DADE |
| | COUNTY NOA AND COMPLETING THE LOCAL |
| | PRODUCT APPROVAL FORM DOWNLOADED FROM |
| | DCA WEBSITE WWW.FLORIDABUILDING.ORG. |
| | |
| | 2- KEY PLAN SHOWS THAT ENTRY DOOR WILL |
| | HAVE SHUTTERS. CONTRACTOR SPECIFIED THAT |
| | ENTRY DOOR WILL BE USED AS THE EMERGENCY |
| | EGRESS AND IS IMPACT RESISTANT. REVISE |
| | KEY PLAN AND INSTALLATION SCHEDULE |
| | SHOWING ENTRY DOOR AS EMERGENCY EGRESS |
| | WITH NO SHUTTERS. |
| | |
| | 3- PROVIDE A COMPLETE INSTALLATION |
| | SCHEDULE WITH THE MINIMUM REQUIRED |
| | INFORMATION. SEE ATTACHED SAMPLE AND |
| | FILL COMPLETELY. |
| | |
| | 4- PANELS FOR OPENING #14 EXCEED THE |
| | MAX. PANEL SPAN SHOWN ON DRAWING 4 OF 7. |
| | REVISE AS REQUIRED. |
| | |
| | 5- THERE ARE TWO DIFFERENT SHUTTER TYPES |
| | SUBMITTED (DIFFERENT GAUGE). CLARIFY |
| | WHICH ONE IS GOING TO BE USED. |
| | |
| | 6- INDICATE IN THE INSTALLATION SCHEDULE |
| | PAGE 5 OF 7 SPECIFIC ANCHOR TYPE AND |
| | SPACING TO BE USED. INFORMATION |
| | SUBMITTED SHOW THE ALL COLUMN BEING |
| | HIGHLIGHTED. INDICATE SPECIFIC ANCHOR |
| | THAT WILL BE USED IN THIS PROJECT. |
| | |