| Plan Review Notes For Permit 04121920 |
| Permit Number |
04121920 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-02 00:00:00 | BUILDING REVIEW PROVISO: | | | **NOTE: PROVIDE THE FOLLOWING | | | INFORMATION PRIOR TO CONSTRUCTION OR | | | INSTALLATION TO AVOID DELAYS/CONFLICTS: | | | 1- IF USING ENTRY DOOR FOR EGRESS AS | | | REQUIRED BY SEC. 1005.4.5 FBC 2001 AND | | | DOOR HAS GLAZING, THEN, GLAZING MUST BE | | | IMPACT PROTECTED OR SOLID DOOR. | | | | | | 2- UPDATE/REVISE TRUSS ANCHOR SCHEDULE | | | AND CALCULATIONS IF CONNECTOR'S CAPACITY | | | AND NUMBER OF NAILS DIFFER FROM THAT | | | TESTED AND PUBLISHED BY MANUFACTURER. | | | **NOTE: CALCULATIONS SHALL COMPLY WITH | | | SECTION 1609.4.3 FBC 2001. | | | | | | 3- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR USP CONNECTORS SPECIFIED ON | | | TRUSS ANCHOR SCHEDULE. PAGE A-6. |
|