| Plan Review Notes For Permit 04121914 |
| Permit Number |
04121914 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-09-10 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM SHOWS A | | | 200A PANEL FOR PANEL "A" WITH 200A OCP | | | FEEDING SAME PANEL, HOWEVER FEEDER SIZES | | | ARE ONLY #1'S. | | | PLEASE SEE 240.4,310.15B6,310.16 | | | | | | 2)NOTE: PLEASE SEE MIN GROUNDING | | | ELECTRODE CONDUCTOR IS TO BE 1/0 FOR A | | | 400A SERVICE AS SHOWN ON RISER. | | | PLEASE SEE A #2 IS CURRENTLY SHOWN WHICH | | | WAS OK FOR PREVIOUS 300A SERVICE. | | | 250.66,31.15B6 | | | | | | 3)NOTE: PLEASE SEE NUMEROUS ITEMS SHOWN | | | ON PLANS AS "OPT". PLEASE SEE THAT ALL | | | OPTIONS AND REVISION ARE TO BE DONE | | | BEFORE ROUGH ELECTRICLA INSPECTION. | | | PLAN ALSO SHOW WASHER AS OPTIONAL, A | | | WASHER IS NOT REQUIRED BY CODE, HOWEVER | | | THE CIRCUIT IS. | | | 210.11C2, 210.52 | | | PLEASE SEE PLANS ALSO DENBOTE THIS | | | REVISION AS BEING THE "AS-BUILT " | | | CONDITION. | | | | | | 4)NOTE: PLEASE SEE GDO'S SHOWN AS .9KW | | | ON PANEL SCHEDULE AND .7KW ON LOAD | | | CALCS, PLEASE CORRELATE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DONOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|