Plan Review Notes
Plan Review Notes For Permit 04121914
Permit Number 04121914
Review Stop B
Sequence Number 3
Notes
Date Text
2005-09-27 00:00:00DENIED BY BUILDING
  
 REVISIONS TO STORM PANELS ARE DENIED.
  
 1) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 2) THE DESIGN LOAD TABLES ARE FOR
 EXPOSURE C AND A MAXIMUM 2:12 ROOF
 PITCH. THE STRUCTURE IS EXPOSURE B WITH
 A 5:12 PITCH ROOF. SHOW HOW THIS TABLE
 WAS USED TO DETERMINE THE PRESSURES
 LISTED IN YOUR INSTALLATION SCHEDULE.
  
 3) THE MEAN ROOF HEIGHT OF THE STRUCTURE
 IS 23'-9" AS SPECIFIED ON THE BUILDING
 PLANS, NOT 26.5'.
  
 4) THE END ZONE FOR THIS STRUCTURE IS
 5.7' WIDE. SOME OF THE OPENINGS ARE
 LOCATED WITHIN THE END ZONE, BUT NONE
 ARE LISTED ON THE INSTALLATION SCHEDULE.
  
 5) SPECIFY THE EDGE DISTANCE ON
 INSTALLATION SCHEDULE.
  
 6) SPECIFY THE FASTENERS ON THE SCHEDULE
 FOR EACH OPENING. SOME OF THE SPACINGS
 THAT ARE HI-LITED ON THE PRODUCT
 APPROVAL DIFFER FROM THE 16" SPACING
 THAT IS LISTED FOR EVERY OPENING ON THE
 INSTALLATION SCHEDULE BASED ON SPAN,
 EDGE DISTANCE, CONNECTION TYPE, ANCHOR
 TYPE AND SUBSTRATE TYPE.
  
 7) OPENING 1 ON THE KEY PLAN SHOULD BE
 ABOVE THE FRONT DOOR.
  
 8) PROVIDE THE OPENING DIMENSIONS ON THE
 KEY PLAN. THE # OF PANELS IS NOT
 NECESSARY AND STEEL GAUGE IS IN THE
 PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  