| Date |
Text |
| 2005-01-06 00:00:00 | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE OVERCURRENT PROTECTION FOR AHU |
| | #2 |
| | & #3 AT 60 AMPS IS TOO LARGE TO PROTECT |
| | A 5KW UNIT.(5000X125%/240=26 AMPS, MAX |
| | 30 AMP OCP). ALSO 60 AMP OCP SHOWN IN |
| | THE MAIN PANEL SEEMS TOO LARGE FOR THE |
| | CONDENSING UNITS. SEE ARTICLE 440.22 |
| | NEC. |
| | |
| | 2} THERE ARE ONLY TWO A/C DISCONNECTS |
| | SHOWN ON THE RISER, BUT THREE UNITS ON |
| | THE PLAN AND IN THE CALC. PLEASE |
| | CORRELATE. |
| | |
| | 3} THERE ARE NO PROVISIONS IN THE |
| | CALCULATIONS FOR POOL EQUIPMENT, BUT |
| | THERE IS EQUIPMENT SHOWN ON THE PLAN. |
| | |
| | 4} IF NOTE #14 IS ADHERED TO, THOSE |
| | CIRCUITS WOULD HAVE TO BE PROTECTED BY |
| | AN AFCI BECAUSE THE DETECTORS ARE |
| | LOCATED IN BEDROOMS. 210.12. |
| | |
| | 5} THE GFI'S SHOWN IN THE DINING ROOM |
| | AND BREAKFAST NOOK, WHILE NOT REQUIRED |
| | ALTHOUGH PERMISSIBLE, MUST BE INSTALLED |
| | IF LEFT ON THE PLAN. |
| | |
| | 6} RECEPTACLES MUST BE ADDED TO THE |
| | MASTER SUITE AND HOBBY ROOM TO COMPLY |
| | WITH 210.52(A). SEE REVIEWED SET OF |
| | PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |