| 2005-01-20 00:00:00 | DENIED |
| | |
| | 1) SPECIFY ON SHEET A3 THAT THE GLASS |
| | BLOCK AT THE ZERO LOT LINE IS ONE HOUR |
| | FIRE RATED. |
| | |
| | 2) ONE OF THE WINDOWS IN BEDROOM #3 |
| | SPECIFIED AS AN EGRESS WINDOW IS MARKED |
| | AS AH33 SH, WHICH DOES NOT MEET EGRESS |
| | REQUIREMENTS. |
| | |
| | 3) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | LISTING INFORMATION FOR THE BBQ AND THE |
| | PREFAB FIREPLACE. |
| | |
| | 4) FBC 1OO7.8.1 REQUIRES STAIR WINDERS |
| | TO HAVE A MINIMUM TREAD DEPTH OF 6 |
| | INCHES AT THE NARROW EDGE AND SHALL HAVE |
| | A MINIMUM TREAD DEPTH OF 11 INCHES AT A |
| | POINT 12 INCHES FROM THE NARROW EDGE. |
| | |
| | 5) PROVIDE DETAILS OF THE HANDRAILS AND |
| | GUARD RAILS AT THE STAIRS. SEE FBC |
| | 1007.5 AND 1015. |
| | |
| | 6) THE WINDLOAD PRESSURES FOR THE 7' X |
| | 5' FIXED GLASS WINDOW AT THE BREAKFAST |
| | NOOK ARE NOT GIVEN. |
| | |
| | 7) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| | ANCHOR BOLTS FOR BUCKET DETAIL 6 ON A7. |
| | |
| | 8) THE DETAIL FOR WOOD FRAME WALL ON A8 |
| | SPECIFIES A USP RT16F AT THE BOTTOM OF |
| | THE WALL AND DETAIL 7 ON A12 SPECIFIES A |
| | USP RT18F AT THE SAME LOCATION. PLEASE |
| | CLARIFY. |
| | |
| | 9) THE GLASS BLOCK DETAIL ON A12 |
| | REFERENCES ASCE 7-88. THE CORRECT |
| | REFERENCE IS ASCE 7-98. |
| | |
| | 10) SECTIONS 1 AND 2 ON ON A13 SPECIFY |
| | FIRE STOPS AT 8" O.C. PLEASE CORRECT. |
| | |
| | 11) THE OWNER AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALCS. PER FBC CHAPTER 13. |
| | |
| | 12) ONLY ONE PRODUCT APPROVAL WAS |
| | SUBMITTED FOR THE SMALL GARAGE DOOR. |
| | |
| | 13) SUBMIT 2 COPIES OF A KEY PLAN FOR |
| | THE STORM PANELS. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR THE |
| | DOUBLE OUTSWING WOOD GLAZED DOORS AT THE |
| | ENTRY. |
| | |
| | 15)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 16) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE MULLIONS DO NOT MEET THE REQUIRED |
| | PRESSURES FOR USE BETWEEN THE 12' |
| | SLIDING GLASS DOOR AND TRANSOM AT THE |
| | FAMILY ROOM. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |