Plan Review Notes
Plan Review Notes For Permit 04121908
Permit Number 04121908
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-07 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE GFI RECEPTS.
  
 2)NOTE: PLEASE SEE HI-HAT LOAD SHOWN AT
 48.0KW. PLEASE SEE 64@75W EACH.
 PLEASE SEE THIS MAY AFFECT SIZE OF
 SERVICE.
  
 3)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 310.15B6,
 250.66
 #2 MIN. (IFF 300A SERVICE REMAINS. )
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATESBRKFST NOOK AS GFI. THIS IS
 NOT REQUIRED,, YET PERMITTED. IF SHOWN
 ON PLANS THEN THIS IS REQUIRED TO BE
 DONE.
  
 5)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS INDICATE METER/MAIN ON
 OUTSIDE OF HOUSE, PANEL IN GARAGE AND
 PANEL IN LAUNDRY RM?
 215.5
  
  
 6)NOTE: PLEASE SEE OCP IS NOT CLEAR ON
 PANEL SCHEDULE/LOAD CALCS FOR AHU 5KE
 HEAT. APPEARS TO BE 50A?
 PLEASE SEE 424.3B 125% MIN AND 150%
 USUALLY MAX. IS THIS 30A OCP?
 PLEASE ALSO SEE RISER SHOWS 60A OCP FOR
 COND UNITS. PLEASE VERIFY THE OCP WITH
 MECH PLANS FOR SIZE OF CU.
  
 7)NOTE: PLEASE SEE 210.52 FOR RECEPT
 LOCATIONS MISSING ON PLANS. BEDRM #2,
 #3, AND DEN.
  
 8)NOTE: PLEASE SEE PLANS INDICATE POOL
 EQUIPMENT, YET THIS IS NOT ON PANEL
 SCHEDULE. IF "FUTURE" PLEASE JUST PLACE
 NOTE ON PLANS FOR "FUTURE".
  
 PLEASE SEE ALL OF THESE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF CONCERN.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SET MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]