Plan Review Notes
Plan Review Notes For Permit 04121902
Permit Number 04121902
Review Stop P
Sequence Number 2
Notes
Date Text
2005-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT A-9 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. CLEANOUT FOR THE WASH MACHINE SHALL
 BE LOCATED 4' ABOVE THE FLOOR. SECTION
 708.10.
 B. THE CABANA BATH IS NOT SHOWN ON THE
 RISER DIAGRAM. SECTION 104.2.1.
 C. THE FUTURE SINK PIPING IS UNCLEAR.
 PLEASE INDICATE IF IT WILL BE LEFT UNDER
 THE SLAB. IF NOT SHOW THE RISER AND
 INDICATE METHOD OF VENT. SECTIONS
 104.2.1. & 901.2.1.
 D. THE FITTING AT THE TOP OF THE RISER
 TO THE SECOND FLOOR DOES NOT DIRECT THE
 WASTE IN THE DIRECTION OF FLOW AS
 REQUIRED IN SECTION 706.3. SEE RED LINE
 EXAMPLE AT TOP OF RISER ONE SET OF
 PLANS.
 2. LOOSE SHEETS ARE NOT ACCEPTABLE.
 PLEASE SUBMIT 2 SETS OF PLANS PER
 SECTIONS 104.2.1, AND 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]