 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2
 & #3 AT 60 AMPS IS TOO LARGE TO PROTECT
 A 5KW UNIT.(5000X125%/240=26 AMPS, MAX
 30 AMP OCP). ALSO 60 AMP OCP SHOWN IN
 THE MAIN PANEL SEEMS TOO LARGE FOR THE
 CONDENSING UNITS. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE ONLY TWO A/C DISCONNECTS
 SHOWN ON THE RISER, BUT THREE UNITS ON
 THE PLAN AND IN THE CALC. PLEASE
 CORRELATE.
  
 3} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 4} IF NOTE #14 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 5} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 6} RECEPTACLES MUST BE ADDED TO THE
 MASTER SUITE AND HOBBY ROOM TO COMPLY
 WITH 210.52(A). SEE REVIEWED SET OF
 PLANS.
  