| Plan Review Notes For Permit 04121896 |
| Permit Number |
04121896 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-01-20 00:00:00 | REDLINED: | | | | | | RISER STILLS SHOWS 2/0'S TO 150A PANELS, | | | THIS IS OK. | | | | | | 2ND FLR ROOM/TECH AREA HAS NOW REMOVED | | | THE RECEPT ON ORIGIANL PLANS. | | | PLEASE SEE RAIL AREA IN A ROOM IS STILL | | | CONSIDERED WALL SPACE PER 210.52 | | | | | | OCP FOR AHU'S, 5KW SHOWS 45A'S? | | | | | | MISSING SD. FIRST FLR, WALL MOUNTED? | | | NFPA-72 8-1.4.2 |
|