Plan Review Notes
Plan Review Notes For Permit 04121896
Permit Number 04121896
Review Stop E
Sequence Number 7
Notes
Date Text
2006-01-20 00:00:00REDLINED:
  
 RISER STILLS SHOWS 2/0'S TO 150A PANELS,
 THIS IS OK.
  
 2ND FLR ROOM/TECH AREA HAS NOW REMOVED
 THE RECEPT ON ORIGIANL PLANS.
 PLEASE SEE RAIL AREA IN A ROOM IS STILL
 CONSIDERED WALL SPACE PER 210.52
  
 OCP FOR AHU'S, 5KW SHOWS 45A'S?
  
 MISSING SD. FIRST FLR, WALL MOUNTED?
 NFPA-72 8-1.4.2