| Plan Review Notes For Permit 04121896 |
| Permit Number |
04121896 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-12-21 00:00:00 | **** PROVISO/REVISION **** | | | | | | PLEASE SEE "PROVISO" GIVEN ON PREVIOUS | | | REVIEW AND NEW NOTES DUE TO CHANGES IN | | | PLANS. | | | | | | | | | 1)NOTE: PLEASE SEE 3#6'S , 1-#10 GRND | | | AND 1#10 NEUTRAL TO POOL SUB PANEL. | | | PLEASE VERIFY THE NUMBER AND SIZE OF | | | CONDUCTORS SHOWN. (SHOWN AS 3-PHASE). | | | | | | 2)NOTE: PLEASE ALSO SEE A #1 GROUNDING? | | | CONDUCTOR SHOWN ON FEEDERS TO SUB | | | PANELS?? | | | | | | 3)NOTE: PLEASE VERIFY OCP FOR BOTH 5KW | | | HEAT STRIPS, AS 45A'S SEEMS HIGH. PLEASE | | | VERIFY. NO CORRECTION NEEDED IF | | | MANUFACTURES NAMEPLATE CORRELATES. | | | | | | 4)NOTE: PLEASE SEE REDLINED PLANS FOR | | | MISSING RECEPTS. | | | PLEASE SEEE WHAT APPEARS TO BE 2' OF | | | WALL IN FAMILY ROOM. | | | PLEASE ALSO SEE 2ND FLR BEDRM #3 , | | | WITHIN 6' OF DOOR. | | | | | | | | | PLEASE REVISE THE ABOVE , SUBMIT FOR | | | REVIEW AND STAMPING BEFORE ROUGH | | | ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|