Plan Review Notes
Plan Review Notes For Permit 04121896
Permit Number 04121896
Review Stop E
Sequence Number 4
Notes
Date Text
2005-11-30 00:00:00REDLINED PLANS/PROVSIO
  
  
  
 1)NOTE: PLEASE SEE 200A OCP FEEDING
 1/0'S (150A) TO 200A PANEL.
 PLEASE SIZE PER 31015B6, 240.4
  
 2)NOTE: PLEASE SEE 3#6'S , 1-#10 GRND
 AND 1#10 NEUTRAL TO POOL SUB PANEL.
 PLEASE VERIFY THE NUMBER AND SIZE OF
 CONDUCTORS SHOWN. (SHOWN AS 3-PHASE).
  
  
  
  
 PLEASE REVISED AND SUBMIT BEFORE FINAL.
 IF ROUGH INSPECTION IS NOT DONE AS OF
 YET, PLEASE REVISE AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]