| 2005-11-30 00:00:00 | REDLINED PLANS/PROVSIO | | | | | | | | | | | | 1)NOTE: PLEASE SEE 200A OCP FEEDING | | | 1/0'S (150A) TO 200A PANEL. | | | PLEASE SIZE PER 31015B6, 240.4 | | | | | | 2)NOTE: PLEASE SEE 3#6'S , 1-#10 GRND | | | AND 1#10 NEUTRAL TO POOL SUB PANEL. | | | PLEASE VERIFY THE NUMBER AND SIZE OF | | | CONDUCTORS SHOWN. (SHOWN AS 3-PHASE). | | | | | | | | | | | | | | | PLEASE REVISED AND SUBMIT BEFORE FINAL. | | | IF ROUGH INSPECTION IS NOT DONE AS OF | | | YET, PLEASE REVISE AT THIS TIME. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|