| 2005-08-23 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- STAIRS WERE REVISED: HANDRAIL HEIGHT |
| | WAS CHANGED TO 34" FROM 38". WHEN |
| | RAILING WAS 38" HIGH IT ALSO SERVED AS A |
| | GUARDRAIL AS REQ'D BY 1015.1 FBC 2001. |
| | NOW, THAT RAILING HEIGHT IS 34" HIGH, |
| | THEN NEED TO PROVIDE A GUARDRAIL. OR, |
| | MIN. RAILING HEIGHT TO BE 36" MIN. SO IT |
| | CAN SERVE ALSO AS A GUARDRAIL. REVISE. |
| | |
| | 2- MEAN ROOF HEIGHT IS GREATER THAN |
| | 25"-0". (MEAN ROOF HEIGHT IS TAKEN FROM |
| | GRADE NOT FROM FIRST FLOOR FINISH |
| | ELEVATION). REVISE MEAN ROOF HEIGHT IN |
| | SHEET A-3 AND REVISE NAILING TYPE AND |
| | SPACING IN ROOF ZONE 3 AS REQ'D BY TABLE |
| | 2306.1CITY AMENDMENTS TO FBC 2001. |
| | NOTE: ZONE 3 IS NOT ONLY AT GABLE ENDS. |
| | IT ALSO INCLUDES ALL CORNERS. SEE FIGURE |
| | 1606.2(C) FBC 2001. |
| | |
| | 3- NUMBER OF RISERS SHOWN ON STAIR SHOP |
| | DRAWINGS ARE DIFFERENT THAN THOSE SHOWN |
| | ON PLANS. REVISE PLANS AS REQUIRED TO |
| | VERIFY COMPLIANCE WITH SEC. 1007.8.3 FBC |
| | |
| | |
| | 4- DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENING AS REQUIRED BY SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 5- PROVIDE FLORIDA/LOCAL PRODUCT |
| | APPROVAL FOR 8'-0" X 8'-0" GARAGE DOOR |
| | THAT MEETS THE DESIGN PRESSURES SHOWN ON |
| | DRAWING #5. |
| | |
| | 6- TRUSS ANCHOR SCHEDULE: REVISE THD210 |
| | FASTENERS. SEE TECHNICAL REPORT FOR |
| | TESTED FASTENERS. |
| | |
| | 7- PROVIDE COMPLETE APPROVED LISTING FOR |
| | BBQ TO BE INSTALLED IN THE PORCH. |
| | INCLUDING, HOOD FOR EXTERIOR USE. |
| | |
| | 8- SHEET A3: CLARIFY WHY NOTE AT BOTTOM |
| | LEFT OF THE PAGE REGARDING IMPACT GLASS |
| | WAS ADDED IF THE PRODUCT APPROVALS |
| | SUBMITTED ARE FOR SHUTTERS & NON-IMPACT |
| | DOORS AND WINDOWS. |
| | |
| | 9- DETAIL B/A-13: REVISE PICKETS |
| | SPACING. 2X WOOD PICKETS @ 6" OF CENTER |
| | WILL ALLOW A 4" SPHERE TO PASS THRU. |
| | NEED TO REDUCE SPACING. SEC. 1015.3 FBC. |
| | |
| | 10- RE-SUBMITTAL AND REVISION FEES FEES |
| | WILL APPLY AT TIME OF RE-RESUBMITTAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |