| Plan Review Notes For Permit 04121896 |
| Permit Number |
04121896 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-24 00:00:00 | ******** UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE SERVICE IS NOW | | | INCREASED TO 400'S, PLEASE SEE GROUNDING | | | ELECTRODE CONDUCTORSHALL BE INCREASED | | | TO 1/0 MIN PER 250.66/310.15B6 | | | | | | 2)NOTE: PLEASE SEE PANEL "A" PANEL | | | SCHEDULE INDICATES PANEL TO BE 200A'? | | | PLEASE SEE RISER SHOWS 150A'S? | | | PLEASE CORRELATE. | | | PLEASE ADJUST ANY FEEDERS ETC FOR ANY | | | INCREASES FOR PANEL SIZE. | | | 310.15B6,240.4 ETC | | | | | | 3)NOTE: PLEASE SEE BOTH PANEL SCHEDULES | | | LIST AHU/SYSTEM #2. (MISPRINT). | | | | | | | | | 4)NOTE: PLEASE SEE WHIRLPOOL TUB IS | | | BEING SHOWN AS FUTURE, IF THIS FOR ROUGH | | | OR ELECTRICAL FINAL, THIS MUST INDICATE | | | OF THIS IS INSTALLED AT THIS TIMEOR | | | NOT. | | | | | | 5)NOTE: PLEASE SEE ONLY ONE ELECTRICAL | | | PANEL SHOWN IN GARAGE AND PLEASE SEE | | | POOL PANEL NOT SHOWN ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|