2005-08-24 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE SERVICE IS NOW
 INCREASED TO 400'S, PLEASE SEE GROUNDING
 ELECTRODE CONDUCTORSHALL BE INCREASED
 TO 1/0 MIN PER 250.66/310.15B6
  
 2)NOTE: PLEASE SEE PANEL "A" PANEL
 SCHEDULE INDICATES PANEL TO BE 200A'?
 PLEASE SEE RISER SHOWS 150A'S?
 PLEASE CORRELATE.
 PLEASE ADJUST ANY FEEDERS ETC FOR ANY
 INCREASES FOR PANEL SIZE.
 310.15B6,240.4 ETC
  
 3)NOTE: PLEASE SEE BOTH PANEL SCHEDULES
 LIST AHU/SYSTEM #2. (MISPRINT).
  
  
 4)NOTE: PLEASE SEE WHIRLPOOL TUB IS
 BEING SHOWN AS FUTURE, IF THIS FOR ROUGH
 OR ELECTRICAL FINAL, THIS MUST INDICATE
 OF THIS IS INSTALLED AT THIS TIMEOR
 NOT.
  
 5)NOTE: PLEASE SEE ONLY ONE ELECTRICAL
 PANEL SHOWN IN GARAGE AND PLEASE SEE
 POOL PANEL NOT SHOWN ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  