2005-06-06 00:00:00SUBMITTAL CHECKLIST:
 1- PROVIDE ATTIC ACCESS AT MASTER
 BEDROOM WING. SEC. 2309.6 FBC 2001.
  
 2- ROOF SHEATHING:A) MEAN ROOF HEIGHT IS
 GREATER THAN 25'-0". REVISE NAILING TYPE
 AND SPACING IN ROOF ZONE 3 AS REQUIRED
 BY TABLE 2306.1 CITY AMENDMENTS TO FBC
 2001.
 B) DIAPHRAGM FOR ROOF ZONES INSHEET
 A-7 CALLS FOR 6" AREA. REVISE AS
 REQUIRED. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
  
 3- STAIR SHOP DRAWINGS NEED TO BE
 REVIEWED AND APPROVED BY ARCHITECT PRIOR
 TO SUBMITTAL TO THIS OFFICE.
  
 4- STAIR DETAIL B/A-13 CALLS FOR 36"
 HIGH RAILING. NOTES ON FLOOR PLANS CALL
 FOR 38" HIGH RAILING. REVISE AS REQUIRED
  
 5- ARCHITECT TO SPECIFY ROOF TILE
 FASTENING AS REQUIRED BY SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
  
 6- DESIGN PRESSURES FOR 8'-0" GARAGE
 DOOR WERE REVISED FROM PREVIOUS
 SUBMITTAL. DESIGN PRESSURES CANN'T BE
 EQUAL FOR A 8'-0" AND A 16'-0" DOOR.
 PROVIDE CALCULATIONS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 7- REVISE TRUSS ANCHOR SCHEDULE. USP
 THD210 OR THD210-2 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY MASONRY
 CONNECTOR. SEE CATALOGUE FOR MASONRY
 CONNECTORS AND REVISE AS REQUIRED.
  
 8- INFORMATION SUBMITTED FOR OUTDOOR BBQ
 NEEDS TO BE APPROVED BY THE BUILDING
 OFFICIAL. HE IS OUT THIS WEEK. I WILL
 FORWARD INFORMATION TO HIM WHEN HE'S
 BACK.
  
 9- DESIGN PARAMETERS CHART ON PAGE A-3:
 CLARIFY WHERE IS THE BASIC VELOCITY
 PRESSURE TAKEN FROM. SEE SECTION 1606
 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.