| 2005-03-25 00:00:00 | BUILDING REVIEW PROVISO: |
| | PROVIDE INFORMATION PRIOR TO |
| | INSTALLATION OR CONTRUCTION TO AVOID |
| | DELAYS OR CONFLICTS. |
| | 1- PROVIDE MANUFACTURER'S SPECS THAT |
| | ALLOW BBQ IN THE PORCH. OTHERWISE, BBQ |
| | WILL NOT BE ALLOWED TO BE INSTALLED IN |
| | PORCH SINCE THEY ARE DESIGNED FOR |
| | OUTDOOR USE ONLY. |
| | |
| | 2- PROVIDE ATTIC ACCESS AT BEDROOM #2 |
| | WING AND AT MASTER BEDROOM WING AS |
| | REQUIRED BY SEC. 2309.6 FBC 2001. |
| | |
| | 3- PROVIDE SMOKE DETECTOR ON FIRST FLOOR |
| | IN CLOSE PROXIMITY TO THE STAIRWAY. AS |
| | REQUIRED BY SEC. 905.2.2 FBC 2001. |
| | |
| | 4- ROOF SHEATHING: MEAN ROOF HEIGHT IS |
| | GREATER THAN 25'. REVISE FASTENER TYPE |
| | AND SPACING FOR ZONES 3. SEE TABLE |
| | 2306.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 5- PROVIDE STAIR SECTION THAT MATCHES |
| | STAIRS SHOWN ON PLANS. |
| | |
| | 6- A) PLANS CALL FOR FLAT CEMENT TILE. |
| | PRODUCT APPROVAL SUBMITTED IS FOR "S". |
| | TILE. REVISE TO MATCH. |
| | B) DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENING AS REQUIRED BY SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 7- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR 8-0" WIDE GARAGE DOOR. |
| | |
| | 8- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE |
| | COMPLETE ENGINEERING CALCS FOR TYPE AND |
| | NUMBER OF FASTENERS THAT DIFFER FROM |
| | THOSE TESTED AND PUBLISHED BY |
| | MANUFACTURER. |
| | NOTE: CALCS TO COMPLY WITH SEC. 1609.4.3 |
| | FBC 2001. |