2005-02-03 00:00:00BUILDING REVIEW CHECKLIST:
 1- SHEET A-2: A) REVISE FOUNDATION NOTE
 #2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
 B OVERLAPPING INFORMATION SHOWN BY THE
 INTERIOR BEARING WALL MAKES INFORMATION
 NOT LEGIBLE TO READ. REVISE AS REQ'D.
  
 2- SHEET A-3: A) HANDRAIL TO BE BETWEEN
 34" AND 38" AS REQ'D BY SEC. 1007.5.1
 FBC 2001 (EXEMPTION #3). REVISE NOTES ON
 SHEETS A-3 AND A-4 AS REQUIRED.
 B) REVISE AREA CALCULATIONS. WHERE IS
 THE 2ND FLOOR BALCONY?
 C) OPENINGS ARE NOT ALLOWED ON ZERO LOT
 LINE WALL. TABLE 600 FBC 2001. REVISE
 LOCATION OF GARAGE VENTILATION OPENING.
 D) NEED COMPLETE BATHROOM WITH DOOR THAT
 ALLOWS 29"MIN. OPENING. SEC. 11-11 FBC.
 BEDROOM #2 HAS THIS NOTE, BUT DOOR SIZE
 SPECIFIED ON BATHROOM IS 2680. REVISE.
 E) REVISE NAME FOR GARAGE NEXT TO BEDRM
 #2. THIS IS ONE CAR GARAGE NOT THREE.
 F) PROVIDE ATTIC ACCESS AT MASTER SUITE
 WING AND AT BEDROOM #2 WING. SECTION
 2309.6 FBC 2001.
 G) NOTE AT BOTTOM OF PAGE CALLS FOR
 MISSILE IMPACT GLAZING, BUT THERE ARE
 STORM SHUTTERS PRODUCT APPROVAL
 SUBMITTED. CLARIFY AS REQUIRED.
  
 3- PROVIDE SMOKE DETECTOR ON FIRST FLOOR
 IN CLOSE PROXIMITY TO THE STAIRWAY
 LEADING TO THE 2ND FL. SEC. 905.2.2
 FBC.
  
 4- ROOF SHEATHING: REVISE FASTENER TYPE
 AND SPACING FOR ROOF AREAS THAT ARE ON
 ZONE 3 WHEN MEAN ROOF HEIGHT IS GREATER
 THAN 25'. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
  
 5- STAIR SECTION ON SHEET A-13 DOESN'T
 MATCH STAIRS SHOWN ON PLANS. PROVIDE
 COMPLETE STAIR SECTION/DETAIL AND SPECS
 THAT MATCH PLANS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 6- ENERGY CALCULATIONS: A) CONDITIONED
 AREA TO MATCH PLANS. REVISE AS
 REQUIRED.
 B) OWNER/AGENT TO SIGN AND DATE FORM.
  
 7- SPECIFICATIONS FOR BBQ SAYS "DO NOT
 INSTALL A GRILL BELOW OVERHEAD
 UNPROTECTED COMBUSTIBLE CONSTRUCTION".
 HOW IS REAR PORCH PROTECTED TO SATISFY
 THIS REQUIREMENT? AND PROVIDE
 MANUFACTURER'S DECLARATION SAYING THAT
 INSTALLATION OF THIS GRILL ON PORCHES IS
 ADEQUATE AND SAFE. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 8- CONCRETE LINTELS: PROVIDE COPY OF
 SAME DADE COUNTY NOA SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
  
 9- STORM SHUTTERS: A) REVISE MIN. AND
 MAX. PANEL SPAN ALLOWED. SEE ENGINEERED
 DRAWINGS FOR LIMITATIONS.
 B) REVISE DESIGN PRESSURES FOR OPENINGS.
 SEE PLANS FOR CALCULATED PRESSURES.
  
 10- PLANS CALL FOR FLAT CEMENT TILE.
 PRODUCT APPROVAL SUBMITTED IS FOR "S"
 TILE. CLARIFY AS REQUIRED.
  
 11- GARAGE DOORS: A) PROVIDE PRODUCT
 APPROVAL FOR 8'-0" WIDE GARAGE DOOR THAT
 MEETS DESIGN PRESSURES CALCULATED ON
 PLANS.
 B) PROVIDE PRODUCT APPROVAL FOR 16'-0"
 WIDE GARAGE DOOR.
  
 12-PROVIDE SAME DADE COUNTY NOA
 SUBMITTED FOR CASEMENT WINDOW FLORIDA
 PRODUCT APPROVAL.
  
 13- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR "INSWING" DOOR AT CABANA
 BATH.
  
 14- SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 15- UPDATE TRUSS ANCHOR SCHEDULE.
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 16- PROVIDE COMPLETE DETAIL/SPECS FOR
 INSTALLATION OF CEILING AT ENTRY AND
 REAR PORCHES. SPECIFY ALL FASTENERS AND
 SPACING. SEE ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
  
 17- SHEET A-8: REVISE CONNECTOR G
 SPECIFIED AT MASONRY WALL ON LEFT SIDE
 OF ROOF. NEED WOOD TO MASONRY CONNECTOR.
  
 SEC. 104.2.1.2 CITY AMENDEMNTS TO FBC
 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.