| 2005-06-08 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENING AS REQUIRED BY SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 2- USP CONNECTOR THD210 AND THD210-2 IS |
| | A WOOD TO WOOD CONNECTOR. NEED MASONRY |
| | CONNECTOR. SEE CATALOGUE FOR PROPER |
| | MASONRY CONNECTOR AND REVISE AS REQUIRED |
| | |
| | 3- BBQ INFORMATION SUBMITTED WILL BE |
| | FORWARDED TO BUILDING OFFICIAL FOR |
| | APPROVAL. |
| | NOTE: THERE ARE SOME COMPANIES WHO HAVE |
| | BBQ'S SPECIFICALLY DESIGNED FOR PORCHES |
| | OR LANAIS. THEY REQUIRE EXHAUST HOOD. |
| | BUILDING OFFICIAL MAY ASK FOR ADDITIONAL |
| | INFORMATION OR TESTING TO SUPPORT |
| | ALFRESCO GRILLS' LETTER STATEMENT THAT |
| | HOOD IS NOT REQUIRED. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 4- WINDOW MULLIONS: CLEARLY SPECIFY |
| | MULLION SIZE AND ANCHORS TO BE USED TO |
| | VERIFY ADEQUACY WITH CALCS FOR DESIGN |
| | PRESSURES AT OPENINGS. |
| | |
| | 5- STORM SHUTTERS: A) REVISE MIN. PANEL |
| | SIZE. SEE ENGINEERED DRAWINGS |
| | LIMITATIONS ACCORDING TO THE MOUNTING |
| | CONDITIONS. |
| | |
| | B) REVISE HEIGHT FOR OPENINGS #13 AND |
| | #14. SEE PLANS FOR OPENINGS. |
| | NOTE: CHECK FOR MAX. PANEL SPAN. |
| | |
| | C) REVISE DESIGN PRESSURES FOR OPENING |
| | #13. SEE PLANS. |
| | NOTE: CHECK FOR MAX. PANEL SPAN. |
| | |
| | 6- DADE COUNTY NOA REPORT FOR CASEMENT |
| | WINDOWSDOESN'T MATCH NOA SUBMITTED FOR |
| | FLORIDA PRODUCT APPROVAL. RESUBMIT |
| | CORRECT ONE. |
| | |
| | 7- DADE COUNTY NOA REPORT FOR CONCRETE |
| | LINTELS DOESN'T MATCH ONE SUBMITTED FOR |
| | FLORIDA PRODUCT APPROVAL. RESUBMIT |
| | CORRECT ONE. |
| | |