| 2005-01-25 00:00:00 | CHECKLIST: |
| | 1-PROVIDE COMPLETE BATHROOM WITH A DOOR |
| | THAT ALLOWS 29" MIN. CLEAR OPENING. |
| | SECTION 11-11 FBC 2001. |
| | |
| | 2-SPECIFY ROOF TILE FASTENING. SECTION |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 3-UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE |
| | COMPLETE ENGINEERING CALCULATIONS FOR |
| | TYPE AND NUMBER OF FASTENERS THAT DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER TO COMPLY WITH SECTION |
| | 1609.4.3 FBC 2001. |
| | |
| | 4- A) TITLE BLOCK NEEDS NAME OF |
| | ARCHITECT SEALING THE PLANS. SEE CHAPTER |
| | 61G1-16004 OF F.A.C. |
| | B) STATE REGISTRATION NUMBER IS |
| | INCORRECT. REVISE AS REQUIRED. |
| | |
| | 5-PROVIDE COMPLETE DETAIL/SPECS FOR |
| | INSTALLATION OF CEILING AT ENTRY AND |
| | REAR PORCH. SPECIFY ALL FASTENERS AND |
| | SPACING. SEE ASTM C926 AND ASTM C1063. |
| | SEC. 2504.2 FBC 2001. |
| | |
| | 6-OWNER/AGENT TO SIGN AND DATE THE |
| | ENERGY CALCULATIONS. |
| | |
| | 7-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) ENTRY DOORS. SEE SIZE ON PLANS. |
| | B) FRENCH DOORS. SEE SIZE ON PLANS. |
| | C) CONCRETE LINTELS: NEED DADE COUNTY |
| | NOA THAT MATCHES ONE SUBMITTED FOR |
| | FLORIDA PRODUCT APPROVAL. |
| | D) FIXED WINDOWS THAT MEET THE DESIGN |
| | PRESSURES CALCULATED ON PLANS. SEE PLANS |
| | FOR SIZE AND LOCATION. |
| | E) ARABESQUE WINDOW AS SHOWN ON PLANS. |
| | |
| | 8- A) PROVIDE COMPLETE UL LISTING AND |
| | SPECS FOR FIREPLACE. SEC. 2806 FBC |
| | 2001. |
| | B) PROVIDE APPROVED BBQ SPECS. SECTION |
| | 2808 FBC 2001. |
| | |
| | 9-STORM SHUTTERS: A) KEY PLAN DOESN'T |
| | MATCH PLANS. |
| | B) REVISED MIN. PANEL SIZE. SEE |
| | ENGINEERED DRAWINGS. |
| | C) REVISE INTERIOR AND END ZONES. SEE |
| | PLANS. |
| | D) REVISE DESIGN PRESSURES. SEE PLANS. |
| | |
| | 10- PROVIDE COMPLETE FRAMING DETAILS FOR |
| | ARABESQUE WINDOW. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 11-OWES $866.23 FOR UPDATED VALUATION. |
| | |
| | 12-REVISE FOUNDATION NOTE #2 ON SHEET |
| | A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER |
| | ACI REFERENCE. |
| | |
| | 13- REVISE CONNECTORS SPECIFIED ON |
| | DETAIL 2/A-9. "SEMCO" IS OUT OF |
| | BUSINESS. |
| | |