| Plan Review Notes For Permit 04121872 |
| Permit Number |
04121872 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-11-22 00:00:00 | ***** UNSAT ***** | | | | | | 1)NOTE: PLEASE SEE MAIN SERVICE IS NOW | | | SHOWN AS 400A'S, PLEASE SEE MIN SIZE FOR | | | GROUNDING ELECTRODE PER 250.66, 1/0 MIN. | | | 310.15B6 | | | | | | 2)NOTE: PLEASE SEE SEE AHU'S #2 AND #3, | | | WHICH ARE BOTH SHOWN AS 5KW HEAT WITH | | | 60A OCP? | | | PLEASE SEE MAX 150% OR MANUFACTURE | | | NAMEPLATE. PLEASE KNOW, IN EITHER CASE | | | 60A OCP IS TOO HIGH FOR A 5KW UNIT. | | | ** PLEASE ALSO VERIFY THE #6 SHOWN AS | | | CONDUCTORS ? | | | | | | 3)NOTE: PLEASE SEE SINGLE GARAGE IS | | | STILL SHOWN AS A THREE-CAR | | | GARAGE(MISPIRNT). | | | | | | 4)NOTE: PLEASE CORRELATE LOADS INDICATED | | | FOR MICRO, DISH, DISP. WITH LOADS ON | | | PANEL SCHEDULES. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE PANEL SCHEDULE "A" | | | SHOWS A DISHWASHER ON A 2-POLE BRKR. | | | PLEASE SEE THIS SEEMS TO BE A MISPRINT | | | AND MAY ALSO BE FOR THE DISPOSAL? | | | PLEASE ALSO UPDATE THE CIRCUIT #'S, IF | | | 2-POLE,,, ETC. | | | | | | 5)NOTE: PLEASE SEE MISSING GFI RECEPT IN | | | KITCHEN PER 210.52C1. PLEASE SEE | | | COUNTERSPACE IS OVER 12" WHICH WOULD | | | REQUIRE ONE MIN. | | | 210.8A6 | | | | | | PLEASE SUBMIT THE ABVOE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|