2005-11-22 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SEE 250.66,310.15B6 FOR
 MIN SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR.
 ** PLEASE SEE SERVICE NOW INCREASED FROM
 300A TO 400A'S.
  
 2)NOTE: PLEASE SEE AHU#2 ON PANEL "B"
 WHICH SHOWS A 5KW UNIT WITH 60A OCP.
 PLEASE ALSO SEE #6 SHOWN.
 PLEAS KNOW, THE #6 IS OK, BUT NOT
 REQUIRED. IF SHOWN AS #6, THEN IT WILL
 BE REQUIRED. PLEASE SEE THE OCP IS TOO
 LARGE FOR A 5KWAHU. (MAX
 150%/MANUFACTURES NAMEPLATE).
  
 3)NOTE: PLEASE SEE DISH/DISP SHOWN AS
 2-POLE, HOWEVER PANEL SCHEDULE ONLY
 SHOWS A SINGLE SPACE/CIRCUIT ON
 SCHEDULE.215.5
 PLEASE CORRELATE.
  
 4)NOTE: PLEASE SEE MICRO,FRIG,DISH/DISP
 LOADS ON PANEL SCHEDULE AND NEUTRAL
 LOADS NEED TO CORRELATE.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PELASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  