| Plan Review Notes For Permit 04121866 |
| Permit Number |
04121866 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-11-22 00:00:00 | **** UNSAT **** | | | | | | | | | 1)NOTE: PLEASE SEE 250.66,310.15B6 FOR | | | MIN SIZE OF THE GROUNDING ELECTRODE | | | CONDUCTOR. | | | ** PLEASE SEE SERVICE NOW INCREASED FROM | | | 300A TO 400A'S. | | | | | | 2)NOTE: PLEASE SEE AHU#2 ON PANEL "B" | | | WHICH SHOWS A 5KW UNIT WITH 60A OCP. | | | PLEASE ALSO SEE #6 SHOWN. | | | PLEAS KNOW, THE #6 IS OK, BUT NOT | | | REQUIRED. IF SHOWN AS #6, THEN IT WILL | | | BE REQUIRED. PLEASE SEE THE OCP IS TOO | | | LARGE FOR A 5KWAHU. (MAX | | | 150%/MANUFACTURES NAMEPLATE). | | | | | | 3)NOTE: PLEASE SEE DISH/DISP SHOWN AS | | | 2-POLE, HOWEVER PANEL SCHEDULE ONLY | | | SHOWS A SINGLE SPACE/CIRCUIT ON | | | SCHEDULE.215.5 | | | PLEASE CORRELATE. | | | | | | 4)NOTE: PLEASE SEE MICRO,FRIG,DISH/DISP | | | LOADS ON PANEL SCHEDULE AND NEUTRAL | | | LOADS NEED TO CORRELATE. | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PELASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|