2005-04-18 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE CORRECT AND RESUBMIT THE
 FOLLOWING CORRECTIONS FOR REVIEW PRIOR
 TO CALLING A ROUGH ELECTRICAL
 INSPECTION.
  
 1} PUT ALL PANELS ON THE PLAN AT CORRECT
 LOCATION.
  
 2} CIRCUITS 12,13 PANEL "A" AND
 12,13,14, AND 15, PANEL "B", NEED TO
 HAVE #12CU FOR THE OCP 20 AMP BREAKER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  