| Plan Review Notes For Permit 04121866 |
| Permit Number |
04121866 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-04-18 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE CORRECT AND RESUBMIT THE | | | FOLLOWING CORRECTIONS FOR REVIEW PRIOR | | | TO CALLING A ROUGH ELECTRICAL | | | INSPECTION. | | | | | | 1} PUT ALL PANELS ON THE PLAN AT CORRECT | | | LOCATION. | | | | | | 2} CIRCUITS 12,13 PANEL "A" AND | | | 12,13,14, AND 15, PANEL "B", NEED TO | | | HAVE #12CU FOR THE OCP 20 AMP BREAKER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|